Plan Review Notes
Plan Review Notes For Permit 18050978
Permit Number 18050978
Review Stop E
Sequence Number 1
Notes
Date Text
2018-06-12 06:00:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL PLAN SUBMITTED FOR REVIEW, ONLY A
 TYPED "SCOPE OF WORK". PROVIDE ELECTRICAL PLAN FOR
 REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. SEPARATE PERMIT REQUIRED FOR LOW VOLTAGE WORK
 (DATA/TV/SPEAKERS ETC.) FBC 105.1
  
 3. THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE
 REVIEW THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC: 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  