| Notes |
| Date |
Text |
| 2018-07-17 05:49:35 | 1) THE SUBMITTED GAS DRAWING REFERS TO A 22KW GENERATOR | | | AT 398,000 BTU'S BUT THE GENERATOR SPECS ARE FOR A 20 | | | KW GENERATOR WITH A RATING OF 281,000 BTU'S AT 100 % | | | LOAD. CLARIFY.2ND REQUEST. | | | 2) SHOW THE SIZE OF THE PIPE AT THE OUTLET OF THE GAS | | | METER.WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST. | | | 3) SHOW THE SIZE AND TYPE OF THE PIPE FROM THE OUTLET | | | OF THE REGULATOR TO THE INTERIOR. WPB AMEND. TO FBC | | | SEC. 107.2.1. 2ND REQUEST. | | | 4) ) A CLOTHES DRYER IS SHOWN ON THE EXISTING GAS PLAN | | | IN CITY RECORDS BUT IS NOT SHOWN ON THIS PLAN. CLARIFY. | | | 2ND REQUEST. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | |
|