Plan Review Notes
Plan Review Notes For Permit 18050951
Permit Number 18050951
Review Stop G
Sequence Number 2
Notes
Date Text
2018-07-17 05:49:351) THE SUBMITTED GAS DRAWING REFERS TO A 22KW GENERATOR
 AT 398,000 BTU'S BUT THE GENERATOR SPECS ARE FOR A 20
 KW GENERATOR WITH A RATING OF 281,000 BTU'S AT 100 %
 LOAD. CLARIFY.2ND REQUEST.
 2) SHOW THE SIZE OF THE PIPE AT THE OUTLET OF THE GAS
 METER.WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
 3) SHOW THE SIZE AND TYPE OF THE PIPE FROM THE OUTLET
 OF THE REGULATOR TO THE INTERIOR. WPB AMEND. TO FBC
 SEC. 107.2.1. 2ND REQUEST.
 4) ) A CLOTHES DRYER IS SHOWN ON THE EXISTING GAS PLAN
 IN CITY RECORDS BUT IS NOT SHOWN ON THIS PLAN. CLARIFY.
 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  