2018-09-19 17:42:513RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18050933
 7/16/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 175 CFMS OF OUTDOOR AIR FOR THE EXERCISE ROOM IS
 INADEQUATE PER TABLE 403.3.1.1 FBC M, AND NEEDS TO BE
 INCREASED TO 385 CFMS. PER THE TABLE THE OCCUPANT
 DENSITY FOR 1,429 SF. IS 15 PERSONS. 15 CFMS/ 20 CFMS
 PER PERSON PLUS 0.6 CFMS/ 1,429 SF. = 385 CFMS. PLEASE
 CORRECT THE CALCULATION ACCORDINGLY. VERIFY THE
 EXISTING SYSTEM HAS THE CAPACITY TO CONDITION THE
 REQUIRED VENTILATION AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  