| 2018-06-05 16:16:41 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050933 |
| | 6/5/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MP: THE FRESH AIR CALCULATIONS ARE INDICATING |
| | THAT AHU #2 WILL HAVE THE DAMPER ADJUSTED TO BRING IN |
| | 1093 CFMS OF OUTDOOR AIR. HOW IS IT POSSIBLE FOR A 3.5 |
| | TON SYSTEM TO CONDITION AND DEHUMIDIFY THAT MUCH AIR? |
| | PLEASE NOTE THAT THE UNIT ITSELF IS LIMITED TO |
| | APPROXIMATELY 1400 CFMS OF SUPPLY AIR, AND TYPICALLY |
| | THE RATIO OF FRESH AIR TO SUPPLY AIR IN A SYSTEM RANGES |
| | FROM 15- 25% OF THE SUPPLY AIR, OR IN THIS CASE |
| | APPROXIMATELY 200-350 CFMS OF FRESH AIR. PLEASE SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE AIR HANDLER |
| | VERIFYING THE SYSTEM CAN PROPERLY CONDITION THAT MUCH |
| | FRESH AIR- SECTION 403.3.1.1 FBC M. |
| | |
| | 2) MP: SHOW THE FRESH AIR DUCTS TO THE TWO AIR HANDLERS |
| | AND INDICATE HOW THE OUTDOOR AIR WILL BE AUTOMATICALLY |
| | CONTROLLED IN COMPLIANCE WITH SECTION C403.2.4.3 FBC EC |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |