Plan Review Notes
Plan Review Notes For Permit 18050933
Permit Number 18050933
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-05 16:16:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050933
 6/5/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MP: THE FRESH AIR CALCULATIONS ARE INDICATING
 THAT AHU #2 WILL HAVE THE DAMPER ADJUSTED TO BRING IN
 1093 CFMS OF OUTDOOR AIR. HOW IS IT POSSIBLE FOR A 3.5
 TON SYSTEM TO CONDITION AND DEHUMIDIFY THAT MUCH AIR?
 PLEASE NOTE THAT THE UNIT ITSELF IS LIMITED TO
 APPROXIMATELY 1400 CFMS OF SUPPLY AIR, AND TYPICALLY
 THE RATIO OF FRESH AIR TO SUPPLY AIR IN A SYSTEM RANGES
 FROM 15- 25% OF THE SUPPLY AIR, OR IN THIS CASE
 APPROXIMATELY 200-350 CFMS OF FRESH AIR. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE AIR HANDLER
 VERIFYING THE SYSTEM CAN PROPERLY CONDITION THAT MUCH
 FRESH AIR- SECTION 403.3.1.1 FBC M.
  
 2) MP: SHOW THE FRESH AIR DUCTS TO THE TWO AIR HANDLERS
 AND INDICATE HOW THE OUTDOOR AIR WILL BE AUTOMATICALLY
 CONTROLLED IN COMPLIANCE WITH SECTION C403.2.4.3 FBC EC
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  