Plan Review Notes
Plan Review Notes For Permit 18050931
Permit Number 18050931
Review Stop E
Sequence Number 2
Notes
Date Text
2018-07-27 15:59:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR
 THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD.
 CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND
 NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%.
 PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO,
 THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A
 WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN
 CALCULATION. MAKE SURE TO INCLUDE ALL LOADS. NEC 220;
 WPB FBC 107.2.1 (LOAD CALCULATION IS NOT CORRECT. THE
 LOAD FOR PANEL PX IS NOT INCLUDED IN THE TOTAL LOAD FOR
 PANEL PTS. PROVIDE CORRECTION AND SEE COMMENT 10
 BELOW.)
 8. CORRECTED.
 9. CORRECTED.
  
 NEW COMMENT:
  
 10. WHEN THE LOAD FOR PANEL PX IS ADDED TO PANEL PTS,
 THE TRANSFORMER, WIRING, PANEL, AND MAIN BREAKER ARE
 ALL UNDERSIZED. PROVIDE CORRECTION. NEC 110.3, 215.2,
 310.15(B)(16), 408.30
 11. ALL OF THE LOAD FOR PANEL PTS IS NOT INCLUDED IN
 THE MAIN SERVICE CALCULATION. PROVIDE CORRECTION. NEC
 220
 12. RISER SHOWS A THREE PHASE FEED TO TRANSFORMER, BUT
 IT APPEARS TO BE A SINGLE PHASE TRANSFORMER. PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  