| 2018-07-27 15:59:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR |
| | THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD. |
| | CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND |
| | NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%. |
| | PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO, |
| | THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A |
| | WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN |
| | CALCULATION. MAKE SURE TO INCLUDE ALL LOADS. NEC 220; |
| | WPB FBC 107.2.1 (LOAD CALCULATION IS NOT CORRECT. THE |
| | LOAD FOR PANEL PX IS NOT INCLUDED IN THE TOTAL LOAD FOR |
| | PANEL PTS. PROVIDE CORRECTION AND SEE COMMENT 10 |
| | BELOW.) |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | |
| | NEW COMMENT: |
| | |
| | 10. WHEN THE LOAD FOR PANEL PX IS ADDED TO PANEL PTS, |
| | THE TRANSFORMER, WIRING, PANEL, AND MAIN BREAKER ARE |
| | ALL UNDERSIZED. PROVIDE CORRECTION. NEC 110.3, 215.2, |
| | 310.15(B)(16), 408.30 |
| | 11. ALL OF THE LOAD FOR PANEL PTS IS NOT INCLUDED IN |
| | THE MAIN SERVICE CALCULATION. PROVIDE CORRECTION. NEC |
| | 220 |
| | 12. RISER SHOWS A THREE PHASE FEED TO TRANSFORMER, BUT |
| | IT APPEARS TO BE A SINGLE PHASE TRANSFORMER. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |