Plan Review Notes
Plan Review Notes For Permit 18050931
Permit Number 18050931
Review Stop E
Sequence Number 1
Notes
Date Text
2018-06-11 17:03:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION PROVIDED FOR SUB-PANEL IS A 3 PHASE
 CALCULATION, BUT THE PANEL IS SINGLE PHASE. PROVIDE
 CORRECTION. NEC 220; WPB FBC 107.2.1
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 6. EMERGENCY LIGHTS AND EXIT SIGNS ARE SHOWN ON CIRCUIT
 20. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 7. LOAD CALCULATION FOR MAIN PANEL USES A DEMAND FACTOR
 THAT IS ONLY PERMITTED FOR THE RECEPTACLE LOAD.
 CONTINUOUS LOADS SHOULD BE CALCULATED AT 125% AND
 NON-CONTINUOUS LOADS SHOULD BE CALCULATED AT 100%.
 PROVIDE ACCURATE LOAD CALCULATION FOR MAIN PANEL. ALSO,
 THIS PLAN AND THE PLAN FOR THE OTHER UNIT EACH SHOW A
 WATER HEATER, BUT ONLY ONE WATER HEATER IS INCLUDED IN
 CALCULATION. MAKE SURE TO INCLUDE ALL LOADS.NEC 220;
 WPB FBC 107.2.1
 8. PROVIDE LOCATION OF ELECTRICAL PANELS AND MAIN
 SERVICE ON PLAN. WPB FBC 107.2.1
 9. THE GFCI DEVICE FOR DRINKING FOUNTAIN MUST BE
 READILY ACCESSIBLE. PROVIDE CORRECTION. NEC 422.5,
 422.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  