Plan Review Notes
Plan Review Notes For Permit 18050930
Permit Number 18050930
Review Stop M
Sequence Number 3
Notes
Date Text
2018-09-20 15:17:373RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18050930
 9/20/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OCCUPANCY CLASSIFICATION OF THE FACILITY HAS
 CHANGED TO I-1 WHCIH REQUIRES THE CORRIDOR WALL TO BE
 1HR. FIRE-RATED PER TABLE 1020.1 FBC B. THIS MAY RESULT
 IN FIRE DAMPERS HAVING TO BE INSTALLED IN SOME DUCT
 PENETRATIONS THROUGH THE CORRIDOR WALLS. PLEASE REVISE
 THE PLANS ACCORDINGLY.
  
 2) SHEET M2: PLEASE MODIFY THE DRYER MAKEUP AIR DETAIL
 TO SHOW THE DUCT RUN AND OPENING INTO THE LAUNDRY ROOM
 ACT CEILING. INDICATE THE DUCT AND INLET GRILL SIZES.
  
 3) M1 & M2: PLEASE LIST THE COOLING, HEATING AND CFM
 SUPPLY CAPACITIES OF THE EXISTING AIR HANDLERS ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  