| 2018-09-20 15:17:37 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050930 |
| | 9/20/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE OCCUPANCY CLASSIFICATION OF THE FACILITY HAS |
| | CHANGED TO I-1 WHCIH REQUIRES THE CORRIDOR WALL TO BE |
| | 1HR. FIRE-RATED PER TABLE 1020.1 FBC B. THIS MAY RESULT |
| | IN FIRE DAMPERS HAVING TO BE INSTALLED IN SOME DUCT |
| | PENETRATIONS THROUGH THE CORRIDOR WALLS. PLEASE REVISE |
| | THE PLANS ACCORDINGLY. |
| | |
| | 2) SHEET M2: PLEASE MODIFY THE DRYER MAKEUP AIR DETAIL |
| | TO SHOW THE DUCT RUN AND OPENING INTO THE LAUNDRY ROOM |
| | ACT CEILING. INDICATE THE DUCT AND INLET GRILL SIZES. |
| | |
| | 3) M1 & M2: PLEASE LIST THE COOLING, HEATING AND CFM |
| | SUPPLY CAPACITIES OF THE EXISTING AIR HANDLERS ON THE |
| | PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |