2018-08-16 11:54:002ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: IN ORDER EXPEDITE THE APPROVAL OF
 THIS PERMIT I SUGGEST A MEETING WITH THE PLAN REVIEWERS
 PRIOR TO RESUBMITTING.
  
 1.SHT. A-3 ON THE DETAIL FOR THE ALTERNATE ROLL IN
 SHOWER IT SHOWS THE WIDTH OF THE SHOWER AT 36" MIN.
 FIN. PER FBC ACC 608.2.3 THE 36" IS AN EXACT DIMENSION
 NOT MIN. OR MAX. PLEASE CLARIFY.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS.THE
 SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH FLOOR
 SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE
 SPRUNG TO RETURN TO A LIFTED POSITION.
  
 3. PLEASE SHOW DIMENSIONS FOR THE CLEAR FLOOR SPACE FOR
 THE TOILETS AND LAVATORY'S. PER FBC ACC 604.3.1, 606.2
  
 4. PLEASE EXPAND THE SANITARY ISOMETRIC DRAWING IT IS
 EXTREMELY CONGESTED AND I AM UNABLE TO DO A
 COMPREHENSIVE REVIEW TO DETERMINE CODE COMPLIANCE. PER
 WPB AMEND TO FBC 107.2.1
  
 5. IT APPEARS THAT THE SANITARY ISOMETRIC IS SHOWING
 THE TWO SOIL STACKS FROM THE SECOND FLOOR CONNECTING
 THROUGH THE THE BATHROOM GROUPS ON THE FIRST FLOOR THEY
 SHALL CONNECT TO THE BUILDING DRAIN SEPARATELY FROM THE
 BATHROOM GROUP. PER FBC PL 912.1, 704.3
  
 6.SHT. THE FLOOR PLAN DOES NOT SHOW THE SOIL STACK THAT
 CONNECTS THE GANG SHOWER, WASHING MACHINES AND THE
 COMMON BATHROOM ON THE SECOND FLOOR PLEASE CLARIFY .
 PER WPB AMEND TO FBC 107.2.1
  
 7. I WAS UNABLE TO DETERMINE THE CODE COMPLIANCE OF THE
 HOT AND COLD WATER ISOMETRIC DRAWING PLEASE EXPAND TO
 SHOW THE FIRST AND SECOND FLOOR SEPARATELY AND NOT NEXT
 TO EACH OTHER. . PER WPB AMEND TO FBC 107.2.1
  
 8. PROVIDE A COMPLETE 1ST AND 2ND FLOOR PLAN SHOWING
 ALL THE HOT AND COLD WATER PIPING AND ALL THE WATER
 HEATERS WITH RECIRCULATION SYSTEMS. . PER WPB AMEND TO
 FBC 107.2.1
  
 9. SHT. P-2 THE 2ND FLOOR FLOOR PLAN SHOWS A 3/4
 PRESSURE RELIEF LINE RUNNING TO THE EXTERIOR OF THE
 BUILDING. THE DISCHARGE PIPING SERVING A PRESSURE
 RELIEF VALVE, TEMPERATURE RELIEF VALVE OR COMBINATION
 THEREOF SHALL:DISCHARGE THROUGH AN AIR GAP LOCATED IN
 THE SAME ROOM AS THE WATER HEATER. PER FBC PL 504.6
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711