| 2018-06-26 17:56:04 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION\ |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A5 THE ROLL IN SHOWER SHALL HAVE A 60" MIN |
| | OPENING AND COMPLY WITH FBC ACC 608.2.2, 608.2.2.1 |
| | 2. THE TRANSFER SHOWER SHALL BE 36"X36" CLEAR INSIDE |
| | DIMENSION AND COMPLY WITH FBC ACC 608.2.2 |
| | 3. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE TO FINISHED FLOOR PLAN SNALL SHOW |
| | COMPLIANCE WITH FBC ACC 609.4 |
| | 4. TOILET PAPER DISPENSER SHALL BE 7" - 9" IN FRONT OF |
| | THE TOILET. PER FBC ACC 604.7 |
| | 5. SHOW COMPLIANCE WITHFBC ACC 610.3 |
| | 6. ON THE SANITARY ISOMETRIC THE VENT FOR THE NEW |
| | UNISEX BATHROOM SHALL REVENT INTO THE VENT STACK ABOVE |
| | TH FLOOD LEVEL RIM OF THE FIXTURES ON THE SECOND FLOOR |
| | IT CANNOT CONNECT TO THE SOIL STACK. PER FBC PL 905.5 |
| | 7. THE SHOWERS IN THE SHOWER ROOM ON THE 2ND FLOOR ARE |
| | NOT VENTED PER FBC PL 901.2.1 |
| | 8. THE SECOND FLOOR SANITARY ISOMETRIC DOES NOT MATCH |
| | THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 9.ON THE SANITARY ISOMETRIC THE LAVATORY IN THE |
| | BATHROOM FOR THE DOUBLE SLEEPING ROOM IS NOT VENTED |
| | COMPLY WITH FBC PL 901.2.1 |
| | 10.SHOW COMPLIANCE WITH FBC PL 504.6 REQUIREMENTS FOR |
| | DISCHARGE PIPING. |
| | |
| | THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE, |
| | TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL: |
| | |
| | |
| | 1.NOT BE DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM. |
| | |
| | |
| | 2.DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME ROOM |
| | AS THE WATER HEATER. |
| | |
| | |
| | 3.NOT BE SMALLER THAN THE DIAMETER OF THE OUTLET OF THE |
| | VALVE SERVED AND SHALL DISCHARGE FULL SIZE TO THE AIR |
| | GAP. |
| | |
| | |
| | 4SERVE A SINGLE RELIEF DEVICE AND SHALL NOT CONNECT TO |
| | PIPING SERVING ANY OTHER RELIEF DEVICE OR EQUIPMENT. |
| | |
| | |
| | 5.DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER |
| | HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE |
| | OUTDOORS. |
| | |
| | |
| | 6.DISCHARGE IN A MANNER THAT DOES NOT CAUSE PERSONAL |
| | INJURY OR STRUCTURAL DAMAGE. |
| | |
| | |
| | 7.DISCHARGE TO A TERMINATION POINT THAT IS READILY |
| | OBSERVABLE BY THE BUILDING OCCUPANTS. |
| | |
| | |
| | 8.NOT BE TRAPPED. |
| | |
| | |
| | 9.BE INSTALLED SO AS TO FLOW BY GRAVITY. |
| | |
| | |
| | 10.TERMINATE NOT MORE THAN 6 INCHES (152 MM) ABOVE AND |
| | NOT LESS THAN TWO TIMES THE DISCHARGE PIPE DIAMETER |
| | ABOVE THE FLOOR OR FLOOD LEVEL RIM OF THE WASTE |
| | RECEPTOR. |
| | |
| | |
| | 11.NOT HAVE A THREADED CONNECTION AT THE END OF SUCH |
| | PIPING. |
| | |
| | |
| | 12.NOT HAVE VALVES OR TEE FITTINGS. |
| | |
| | 11. SHOW COMPLIANCE WITH FBC PL 607.2 HOT OR TEMPERED |
| | WATER SUPPLY TO FIXTURES.THE DEVELOPED LENGTH OF HOT OR |
| | TEMPERED WATER PIPING, FROM THE SOURCE OF HOT WATER TO |
| | THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, SHALL |
| | NOT EXCEED 50 FEET (15 240 MM). RECIRCULATING SYSTEM |
| | PIPING AND HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE |
| | SOURCES OF HOT OR TEMPERED WATER. |
| | |
| | 12. TEMPERED WATER REQUIRED AT LAVATORY IN UNISEX |
| | BATHROOM PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC |
| | HAND-WASHING FACILITIES. TEMPERED WATER SHALL BE |
| | DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES |
| | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR |
| | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL |
| | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |