Plan Review Notes
Plan Review Notes For Permit 18050930
Permit Number 18050930
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-26 17:56:041ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION\
  
 PLUMBING COMMENTS:
  
 1. SHT. A5 THE ROLL IN SHOWER SHALL HAVE A 60" MIN
 OPENING AND COMPLY WITH FBC ACC 608.2.2, 608.2.2.1
 2. THE TRANSFER SHOWER SHALL BE 36"X36" CLEAR INSIDE
 DIMENSION AND COMPLY WITH FBC ACC 608.2.2
 3. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE TO FINISHED FLOOR PLAN SNALL SHOW
 COMPLIANCE WITH FBC ACC 609.4
 4. TOILET PAPER DISPENSER SHALL BE 7" - 9" IN FRONT OF
 THE TOILET. PER FBC ACC 604.7
 5. SHOW COMPLIANCE WITHFBC ACC 610.3
 6. ON THE SANITARY ISOMETRIC THE VENT FOR THE NEW
 UNISEX BATHROOM SHALL REVENT INTO THE VENT STACK ABOVE
 TH FLOOD LEVEL RIM OF THE FIXTURES ON THE SECOND FLOOR
 IT CANNOT CONNECT TO THE SOIL STACK. PER FBC PL 905.5
 7. THE SHOWERS IN THE SHOWER ROOM ON THE 2ND FLOOR ARE
 NOT VENTED PER FBC PL 901.2.1
 8. THE SECOND FLOOR SANITARY ISOMETRIC DOES NOT MATCH
 THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 9.ON THE SANITARY ISOMETRIC THE LAVATORY IN THE
 BATHROOM FOR THE DOUBLE SLEEPING ROOM IS NOT VENTED
 COMPLY WITH FBC PL 901.2.1
 10.SHOW COMPLIANCE WITH FBC PL 504.6 REQUIREMENTS FOR
 DISCHARGE PIPING.
  
 THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE,
 TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL:
  
  
 1.NOT BE DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM.
  
  
 2.DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME ROOM
 AS THE WATER HEATER.
  
  
 3.NOT BE SMALLER THAN THE DIAMETER OF THE OUTLET OF THE
 VALVE SERVED AND SHALL DISCHARGE FULL SIZE TO THE AIR
 GAP.
  
  
 4SERVE A SINGLE RELIEF DEVICE AND SHALL NOT CONNECT TO
 PIPING SERVING ANY OTHER RELIEF DEVICE OR EQUIPMENT.
  
  
 5.DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER
 HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE
 OUTDOORS.
  
  
 6.DISCHARGE IN A MANNER THAT DOES NOT CAUSE PERSONAL
 INJURY OR STRUCTURAL DAMAGE.
  
  
 7.DISCHARGE TO A TERMINATION POINT THAT IS READILY
 OBSERVABLE BY THE BUILDING OCCUPANTS.
  
  
 8.NOT BE TRAPPED.
  
  
 9.BE INSTALLED SO AS TO FLOW BY GRAVITY.
  
  
 10.TERMINATE NOT MORE THAN 6 INCHES (152 MM) ABOVE AND
 NOT LESS THAN TWO TIMES THE DISCHARGE PIPE DIAMETER
 ABOVE THE FLOOR OR FLOOD LEVEL RIM OF THE WASTE
 RECEPTOR.
  
  
 11.NOT HAVE A THREADED CONNECTION AT THE END OF SUCH
 PIPING.
  
  
 12.NOT HAVE VALVES OR TEE FITTINGS.
  
 11. SHOW COMPLIANCE WITH FBC PL 607.2 HOT OR TEMPERED
 WATER SUPPLY TO FIXTURES.THE DEVELOPED LENGTH OF HOT OR
 TEMPERED WATER PIPING, FROM THE SOURCE OF HOT WATER TO
 THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, SHALL
 NOT EXCEED 50 FEET (15 240 MM). RECIRCULATING SYSTEM
 PIPING AND HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE
 SOURCES OF HOT OR TEMPERED WATER.
  
 12. TEMPERED WATER REQUIRED AT LAVATORY IN UNISEX
 BATHROOM PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC
 HAND-WASHING FACILITIES. TEMPERED WATER SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  