| 2018-06-18 16:13:24 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050930 |
| | 6/19/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: THE AMOUNT OF RETURN AIR TAKEN FROM EACH |
| | SLEEPING ROOM SHALL NOT BE GREATER THAN THE FLOW RATE |
| | OF SUPPLY AIR DELIVERED TO THE SPACE- SECTION 601.5 (3) |
| | FBC M |
| | |
| | 2) M2, LAUNDRY: A) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE NEW DRYERS, THE EXHAUST DUCT WORK, AND |
| | TERMINATION CAP- SECTION 504.1. B) INDICATE HOW MAKEUP |
| | AIR IS BEING PROVIDED FOR THE DRYERS AND PROVIDE A |
| | CALCULATION- SECTION 504.6. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |