2018-06-25 13:42:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. CURRENT LOAD CALCULATION DOES NOT
 SHOW ALL LOADS. ADDITIONALLY, THERE IS A DEMAND FACTOR
 OF 50% USED FOR LOAD OVER 10,000 VA WHICH IS A CODE
 VIOLATION. THIS DEMAND FACTOR IS ONLY TO BE USED FOR
 RECEPTACLE OUTLET LOAD, NOT FOR THE ENTIRE LOAD. ANY
 CONTINUOUS LOADS SHOULD BE CALCULATED AT 125%. PROVIDE
 LOAD FOR PANEL L-2 AND FOR ENTIRE SERVICE. NEC 215.2,
 220, TABLE 220.44, 408.30
 2. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  