Plan Review Notes
Plan Review Notes For Permit 18050927
Permit Number 18050927
Review Stop B
Sequence Number 1
Notes
Date Text
2018-05-27 14:42:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID.
  
 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEET, FBC 107.
  
 3. THE ASSEMBLY SELECTED HAS A DESIGN PRESSURE
 LIMITATION OF -52.5 WHICH DOES NOT MEET THE
 REQUIREMENTS OF ZONES 2 AND 3. SEE GENERAL LIMITATION
 #7 ON PAGE 4 OF 5, ENGINEERING REQUIRED.
  
 4. A PRE INSPECTION IS REQUIRED PRIOR TO COMMENCEMENT.
 INSPECTOR WILL VERIFY THAT SHEATHING IS IN GOOD
 CONDITION, AND THAT ONLY ONE ROOF IS CURRENTLY
 INSTALLED, FBC 107. IT IS CONTRACTOR'S RESPONSIBILITY
 TO SCHEDULE THIS INSPECTION PRIOR TO COMMENCEMENT,
 AFTER PERMIT IS ISSUED.
  
  
  
  
  