| Plan Review Notes For Permit 18050924 |
| Permit Number |
18050924 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-22 09:11:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) IT APPEARS, THROUGH THE INDICATED DESIGN CIRLCES, | | | THAT THE FAN # 3 IS WITHIN THE 10' MINIMUM CLEARENCE | | | REQUIREMENT OF NFPA 96 OF AHU INTAKE 1-1. | | | | | | PER NFPA 96 | | | | | | 7.8.2 ROOFTOP TERMINATIONS. | | | 7.8.2.1 ROOFTOP TERMINATIONS SHALL BE ARRANGED WITH OR | | | PROVIDED | | | WITH THE FOLLOWING: | | | (1) A MINIMUM OF 3 M (10 FT) OF HORIZONTAL CLEARANCE | | | FROM | | | THE OUTLET TO ADJACENT BUILDINGS, PROPERTY LINES, AND | | | AIR | | | INTAKES | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE | | | REFERENCE OR ACTUAL SCALED DIMENSIONS. | | | | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|