| Plan Review Notes For Permit 18050905 |
| Permit Number |
18050905 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-06-30 04:15:10 | 1) THE TDH CALCULATIONS MUST INCCLUDE ALL THE SYSTEM | | | COMPONENTS IN THE PIPING SYSTEM INCLUDING THE FILTER. | | | THIS HAS NOT BEEN DONE.SUBMIT NEW TDH CALCULATIONS. | | | 2) IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS | | | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS | | | IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE | | | TDH CALCULATIONS. | | | 3) INDICATE ON THE POOL PUMP SPECS WHICH PUMP IS BEING | | | INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) COMPILE ALL THE DOCUMENTS AND PLANS INTO TWO | | | COMPLETE SETS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|