| Plan Review Notes For Permit 18050880 |
| Permit Number |
18050880 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-03 10:25:46 | 1) THE SUBMITTED GAS DRAWING REFERS TO A 22KW GENERATOR | | | AT 398,000 BTU'S BUT THE GENERATOR SPECS ARE FOR A 20 | | | KW GENERATOR WITH A RATING OF 281,000 BTU'S AT 100 % | | | LOAD. CLARIFY. | | | 2) THE EXHAUST FROM THE GENERATOR SHALL BE LOCATED A | | | MINIMUM OF 10 FEET FROM ANY BUILDING OPENING INCLUDING | | | ATTIC/SOFFIT VENTS. | | | 3) SHOW THE SIZE AND TYPE OF PIPE AT THE OUTLET OF THE | | | GAS METER.WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) SHOW THE SIZE AND TYPE OF PIPE FROM THE OUTLET OF | | | THE REGULATOR TO THE INTERIOR. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 5) IDENTIFY ON THE REGULATOR SPECS WHICH SPECIFIC MODEL | | | IS BEING INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) A CLOTHES DRYER IS SHOWN ON THE EXISTING GAS PLAN IN | | | CITY RECORDS BUT IS NOT SHOWN ON THIS PLAN. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | |
|