2018-08-07 12:45:382ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER DIAGRAM
 IT IS CONFUSING BECAUSE OF THE NUMBER OF REGULATORS
 YOUR SHOWING, A SET OF REGULATORS ON THE TANKS ONE
 BEFORE THE FIRST TEE, TWO AFTER THE TEE AND ONE AT EACH
 APPLIANCE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 YOUR SHOWING THREE DIFFERENT REGULATOR WHICH WOULD
 THREE SYSTEM PRESSURES PLEASE SHOW THEM ON THE RISER
 AND IF THE PRESSURE IS UNDER 2PSI INDICATE IN INCHES OF
 WATER COLUMN.
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR LP TANKS. PER
 WPB AMEND TO FBC 107.2.1 IF YOU GOING TO SUBMIT THE
 INFORMATION SPECIFICATION AND TANK DRAWING SETBACKS AND
 SITE DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS
 OF TANKS FROM THIS SET OF PLANS
  
 4.SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS REGULATORS TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 5. CLEARLY SHOW THE CAPACITY OF LP TANK(S), TYPE OF
 TANK (DOT OR ASME), THE DISTANCE OF THE TANK FROM THE
 EXTERIOR BUILDING WALL AND ADJACENT PROPERTY LINES, THE
 DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2. IF YOU GOING TO SUBMIT THE
 INFORMATION SPECIFICATION AND TANK DRAWING SETBACKS AND
 SITE DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS
 OF TANKS FROM THIS SET OF PLANS
  
  
 6. CLEARLY INDICATE ON THE PLAN THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. AND THE TANK SHALL BE SECURELY ANCHORED TO
 WITHSTAND 170 MPH ULT WIND LOAD PER THE FLORIDA
 BUILDING CODE. IF YOU GOING TO SUBMIT THE INFORMATION
 SPECIFICATION AND TANK DRAWING SETBACKS AND SITE
 DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS OF
 TANKS FROM THIS SET OF PLANS
  
 7. FOR THE SIZING TABLE THE INFORMATION YOU PROVIDED IS
 CONFUSING PLEASE CLARIFY, A) UNDER THE NOTES ON SHT P2
 YOU LIST TABLE 402.2 THERE IS NO TABLE UNDER THAT
 SECTION, B) IF YOU GOING TO USE THE EQUATION METHOD 4-1
 SHOW THE EQUATIONS FOR EACH SIZE ON THE PLAN. C)
 SECTIONS 402.4.1, 402.4.2, 402.4.2 ARE DIFFERENT SIZING
 METHODS PLEASE CLARIFY WHICH ONE YOU ARE USING. IT
 WOULD MAKE IT MUCH SIMPLER IF YOU JUST SPECIFIED THE
 TABLE 402.4(25)(26)(27)(28)
  
 NEW COMMENT:
  
 1. THE CONVECTION OVEN IS NOT SHOWN ON THE RISER
 DIAGRAM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  