| 2018-08-07 12:45:38 | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| | |
| | 1. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER DIAGRAM |
| | IT IS CONFUSING BECAUSE OF THE NUMBER OF REGULATORS |
| | YOUR SHOWING, A SET OF REGULATORS ON THE TANKS ONE |
| | BEFORE THE FIRST TEE, TWO AFTER THE TEE AND ONE AT EACH |
| | APPLIANCE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | YOUR SHOWING THREE DIFFERENT REGULATOR WHICH WOULD |
| | THREE SYSTEM PRESSURES PLEASE SHOW THEM ON THE RISER |
| | AND IF THE PRESSURE IS UNDER 2PSI INDICATE IN INCHES OF |
| | WATER COLUMN. |
| | |
| | 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR LP TANKS. PER |
| | WPB AMEND TO FBC 107.2.1 IF YOU GOING TO SUBMIT THE |
| | INFORMATION SPECIFICATION AND TANK DRAWING SETBACKS AND |
| | SITE DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS |
| | OF TANKS FROM THIS SET OF PLANS |
| | |
| | 4.SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS REGULATORS TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 5. CLEARLY SHOW THE CAPACITY OF LP TANK(S), TYPE OF |
| | TANK (DOT OR ASME), THE DISTANCE OF THE TANK FROM THE |
| | EXTERIOR BUILDING WALL AND ADJACENT PROPERTY LINES, THE |
| | DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| | PER NFPA 58, TABLE 3-2.2.2. IF YOU GOING TO SUBMIT THE |
| | INFORMATION SPECIFICATION AND TANK DRAWING SETBACKS AND |
| | SITE DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS |
| | OF TANKS FROM THIS SET OF PLANS |
| | |
| | |
| | 6. CLEARLY INDICATE ON THE PLAN THE METHOD OF REQUIRED |
| | PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA |
| | 58. AND THE TANK SHALL BE SECURELY ANCHORED TO |
| | WITHSTAND 170 MPH ULT WIND LOAD PER THE FLORIDA |
| | BUILDING CODE. IF YOU GOING TO SUBMIT THE INFORMATION |
| | SPECIFICATION AND TANK DRAWING SETBACKS AND SITE |
| | DRAWINGS UNDER A SEPARATE PERMIT REMOVE DRAWINGS OF |
| | TANKS FROM THIS SET OF PLANS |
| | |
| | 7. FOR THE SIZING TABLE THE INFORMATION YOU PROVIDED IS |
| | CONFUSING PLEASE CLARIFY, A) UNDER THE NOTES ON SHT P2 |
| | YOU LIST TABLE 402.2 THERE IS NO TABLE UNDER THAT |
| | SECTION, B) IF YOU GOING TO USE THE EQUATION METHOD 4-1 |
| | SHOW THE EQUATIONS FOR EACH SIZE ON THE PLAN. C) |
| | SECTIONS 402.4.1, 402.4.2, 402.4.2 ARE DIFFERENT SIZING |
| | METHODS PLEASE CLARIFY WHICH ONE YOU ARE USING. IT |
| | WOULD MAKE IT MUCH SIMPLER IF YOU JUST SPECIFIED THE |
| | TABLE 402.4(25)(26)(27)(28) |
| | |
| | NEW COMMENT: |
| | |
| | 1. THE CONVECTION OVEN IS NOT SHOWN ON THE RISER |
| | DIAGRAM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |