Plan Review Notes
Plan Review Notes For Permit 18050859
Permit Number 18050859
Review Stop E
Sequence Number 2
Notes
Date Text
2018-07-27 10:17:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 (TEXT IN RISER DIAGRAM IS
 ILLEGIBLE. PROVIDE CORRECTED RISER DIAGRAM WHERE ALL
 INFORMATION IS LEGIBLE.)
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 (PANEL
 SCHEDULES FOR EACH PANEL NOT PROVIDED, MUST HAVE EACH
 PANEL SCHEDULE. CIRCUITS ARE NOT IDENTIFIED AS NEW OR
 EXISTING, PROVIDE CORRECTION.)
 4. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
 (THIS SHOULD BE FOR THE TOTAL OF THE JOB, NOT JUST
 MECHANICAL AND ELECTRICAL. PROVIDE AS PREVIOUSLY
 REQUESTED.)
  
 NEW COMMENTS:
  
 5. LOAD CALCULATION PROVIDED FOR EACH PANEL SCHEDULE IS
 THE TYPE OF CALCULATION USED FOR RESIDENTIAL
 INSTALLATIONS. PROVIDE LOAD CALCULATION FOR SERVICE AND
 EACH PANEL, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 6. NOTE BELOW RISER DIAGRAM STATES THIS DESIGN IS BASED
 ON 2008 ENERGY CONSERVATION, WHICH IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (SEE ABOVE)
 7. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 8. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 9. PLAN SHOWS AN AIC CALCULATION THAT IS NOT COMPLETE.
 AIC CALCULATION IS NOT REQUIRED UNLESS THERE IS SERVICE
 EQUIPMENT BEING ADDED. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1; NEC 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  