| 2018-07-27 10:17:32 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30 (TEXT IN RISER DIAGRAM IS |
| | ILLEGIBLE. PROVIDE CORRECTED RISER DIAGRAM WHERE ALL |
| | INFORMATION IS LEGIBLE.) |
| | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 (PANEL |
| | SCHEDULES FOR EACH PANEL NOT PROVIDED, MUST HAVE EACH |
| | PANEL SCHEDULE. CIRCUITS ARE NOT IDENTIFIED AS NEW OR |
| | EXISTING, PROVIDE CORRECTION.) |
| | 4. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE |
| | OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| | (THIS SHOULD BE FOR THE TOTAL OF THE JOB, NOT JUST |
| | MECHANICAL AND ELECTRICAL. PROVIDE AS PREVIOUSLY |
| | REQUESTED.) |
| | |
| | NEW COMMENTS: |
| | |
| | 5. LOAD CALCULATION PROVIDED FOR EACH PANEL SCHEDULE IS |
| | THE TYPE OF CALCULATION USED FOR RESIDENTIAL |
| | INSTALLATIONS. PROVIDE LOAD CALCULATION FOR SERVICE AND |
| | EACH PANEL, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 6. NOTE BELOW RISER DIAGRAM STATES THIS DESIGN IS BASED |
| | ON 2008 ENERGY CONSERVATION, WHICH IS NOT THE CURRENT |
| | CODE. PROVIDE CORRECTION. FBC PREFACE (SEE ABOVE) |
| | 7. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 8. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 |
| | 9. PLAN SHOWS AN AIC CALCULATION THAT IS NOT COMPLETE. |
| | AIC CALCULATION IS NOT REQUIRED UNLESS THERE IS SERVICE |
| | EQUIPMENT BEING ADDED. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. WPB FBC 107.2.1; NEC 110.10 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |