| 2018-06-07 17:51:21 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW THE SYSTEM PRESSURE ON THE RISER DIAGRAM |
| | IT IS CONFUSING BECAUSE OF THE NUMBER OF REGULATORS |
| | YOUR SHOWING, A SET OF REGULATORS ON THE TANKS ONE |
| | BEFORE THE FIRST TEE, TWO AFTER THE TEE AND ONE AT EACH |
| | APPLIANCE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR LP TANKS. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. THE PLAN IS SHOWING 2 LP TANKS BUT THE NOTE ON THE |
| | RISER IS LISTING 3 PLEASE CLARIFY. . PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 5. CLEARLY SHOW THE CAPACITY OF LP TANK(S), TYPE OF |
| | TANK (DOT OR ASME), THE DISTANCE OF THE TANK FROM THE |
| | EXTERIOR BUILDING WALL AND ADJACENT PROPERTY LINES, THE |
| | DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| | PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 6. CLEARLY INDICATE ON THE PLAN THE METHOD OF REQUIRED |
| | PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA |
| | 58. AND THE TANK SHALL BE SECURELY ANCHORED TO |
| | WITHSTAND 170 MPH ULT WIND LOAD PER THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 7. I CANNOT VERIFY PIPE SIZINGOF THE SYSTEM PLEASE |
| | CLARIFY THE FOLLOWING |
| | A) SYSTEM PRESSURE |
| | B) THE TABLE LISTED 402.4(2)(3)(20) ARE FOR NATURAL |
| | GAS, IF SYSTEM IS LP GAS PROVIDE THOSE SIZING TABLES. |
| | |
| | 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| | 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |