| 2018-06-20 11:49:11 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY AND SHALL |
| | STATE THAT ON THE PLAN PER FBC EX 506 AND SHALL COMPLY |
| | WITH FBCEX CH 10 |
| | |
| | 2. PLEASE SHOW THE REQUIRED FLOOR SPACE IN THE ADA |
| | BATHROOM AND LABEL CLEAR FLOOR SPACE WITH DIMENSIONS |
| | PER FBC ACC 304.3.1, 604.3.1 , 606.2 |
| | |
| | 3. PLEASE LABEL THE DRINKING FOUNTAIN AND SERVICE SINK |
| | ON THE FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. THE DRINKING FOUNTAIN SHALL HAVE A SPOUT FOR A |
| | STANDING PERSON AND A LOWER ONE FOR SOMONE IN A WHEEL |
| | CHAIR A HILO DRINKING FOUNTAIN COMPLIES PER FBC ACC |
| | 211.2 |
| | |
| | 5. SHT. A-2 THE THE DETAIL FOR THE CLEAR FLOOR SPACE |
| | AROUND THE TOILET IS NON COMPLIANT PLEASE SHOW |
| | COMPLIANT DIMENSIONS PER FBC ACC 604.3.1 |
| | |
| | 6. THE GRAB BARS SHALL BE MEASURE FROM THE TOP OF THE |
| | GRIPPING SURFACE FROM FINISHED FLOOR PER FBC ACC 609.4 |
| | |
| | 7. PROVIDE A WATER ISOMETRIC. WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 8, THE BREAK ROOM SINK SHALL BE ACCESSIBLE AND COMPLY |
| | WITH FBC ACC 212.3 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |