| 2018-06-18 17:17:40 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050851 |
| | 6/18/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX= FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVBIDE MECHANICAL PLANS SHOWING ALL |
| | REQUIRED ALTERATIONS TO THE EXISTING SYSTEMS TO |
| | ACCOMODATE THE NEW FLOOR PLAN LAYOUT AND THE CHANGE OF |
| | OCCUPANCY. PLEASE INCLUDE VENTILATUION CALCULATIONS FOR |
| | ALL ROOMS AND SPACES IN COMPLIANCE WITH TABLE 403.3.1 |
| | FBC M. |
| | |
| | 2) AS STATED IN COMMENT #1 ABOVE, THE PROPOSED PROJECT |
| | APPEARS TO BE A CHANGE OF OCCUPANCY AS DEFINED IN |
| | SECTION 202 FBC EX. PLEASE SEE CHAPTER 10 FOR ALL |
| | REQUIRED COMPLIANCES, AND INDICATE THE CLASSIFICATION |
| | OF WORK ON COVER SHEET T-1 PER SECTION 506 FBC EX. |
| | |
| | 3) REFER TO SECTION C505.1 FBC EC SND SUBMIT AN ENERGY |
| | COMPLIANCE REPORT FOR THWE PROPOSED CHANGE OF |
| | OCCUPANCY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |