| 2018-06-16 16:00:05 | ****CORRECTIONS**** |
| | REVISED 6/20/18 |
| | REVISED 6/28/18 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED |
| | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | 2. PROVIDE INFORMATION ABOUT THE PREVIOUS PERMITTED |
| | OCCUPANCY; IS THIS A CHANGE OF OCCUPANCY? IF YES, |
| | REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER 10. |
| | |
| | 3. THIS PROPERTY HAS A NUMBER OF EXPIRED PERMITS; |
| | PLEASE RESOLVE AT THIS TIME. AS DISCUSSED, AT LEAST |
| | THREE OF THE PERMITS WERE FOR THE SUBJECT UNIT. THERE |
| | IS AN EXPIRED ELECTRICAL PERMIT WHICH FAILED |
| | INSPECTION. |
| | |
| | 4. PLAN SHOW OCCUPANCY AS "WAREHOUSE" WITH 500 SF PER |
| | PERSON, BUT THE PLAN ALSO STATES THAT THIS IS A |
| | "SHOWROOM". A SHOWROOM IS MERCANTILE FBC B 309.1, 60 SF |
| | PER PERSON, FBC B 1004. |
| | |
| | 5. PROVIDE A DETAIL FOR THE BREAK ROOM SINK, FBC A |
| | 212.3, 606. |
| | |
| | 6. PLAN STATES THAT ADA BATHROOM IS "EXISTING", BUT THE |
| | DETAILS ARE STANDARD DETAILS. PROVIDE DETAILS OF THE |
| | EXISTING TO SHOW COMPLIANCE, FBC 107. |
| | |
| | 7. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD, FBC 107. |
| | |
| | 8. DOES THIS SPACE HAVE AN ACCESSIBLE ROUTE, FROM |
| | ACCESSIBLE PARKING TO THE ENTRANCE? FBC A 202.4. REVISE |
| | PLAN TO SHOW COMPLIANCE. |
| | |
| | 9. REVISED 6/28/18 PURSUANT TO MEETING WITH DOUG |
| | HARVEY, ABO, RICHARD COHEN ATTY, & OWNER |
| | |
| | THIS BUILDING HAS A NUMBER OF EXPIRED PERMITS. AS |
| | DISCUSSED, INCORPORATE THE PERMITS WHICH AFFECT THIS |
| | UNIT INTO THIS PERMIT: |
| | |
| | 05011183, CUT WALL AND INSTALL GARAGE DOOR 9'X8' |
| | 06082252, TAKE DOWN WALL IN BAY 2-3 AND BUILD FIRE |
| | RATED WALL |
| | 06082253, ELECTRICAL FOR 06082252 |
| | |
| | THIS PERMIT WILL BE ISSUED WITH PROVISO; RESOLUTION OF |
| | EXPIRED ELECTRICAL PERMIT 08070213 REQUIRED PRIOR TO |
| | FINAL INSPECTION. |
| | |
| | 10. (NEW 6/28) THE PLAN INDICATES "EXISTING FIRE |
| | WALLS". PLEASE SEE EXPIRED PERMITS 06082252, 10070718. |
| | AS FINAL INSPECTIONS WERE NOT OBTAINED, THE WALLS ARE |
| | NOT CONSIDERED "EXISTING". THIS WORK SHOULD BE |
| | INCORPORATED INTO THIS PERMIT. |
| | |
| | 11. (NEW 6/28) PROVIDE INFORMATION TO SHOW COMPLIANCE |
| | WITH FBC B TABLE 506.2. IS THE BUILDING SPRINKLERED? |
| | WHAT IS THE BUILDING TYPE? |
| | |
| | |
| | |
| | |
| | |
| | |
| | |