Plan Review Notes
Plan Review Notes For Permit 18050850
Permit Number 18050850
Review Stop G
Sequence Number 2
Notes
Date Text
2018-06-11 16:42:4306/11/2018 2ND GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) THE GAS METER AC-250 HAS A MAX OUTPUT OF 560 BTU'S @
 12" W.C AND 610 BTU'S @ 2PSI AND WOULD BE UNDERSIZED.
 1" SCH 40 PIPING BASED OFF FBC FUEL AND GAS 402.4 (1)
 LIST A MAX BTU FLOW OF 514 BTU'S. YOU ENTIRE SYSTEM IS
 UNDERSIZED .WHAT IS YOUR INTENT ON UPGRADING IF
 NECESSARY AS PER YOUR COMMENT ON THE PLAN? FBC 107.2.1
  
 2) YOU REFERENCE NFPA 15 ON YOUR PLAN. NFPA 15 DOES NOT
 APPLY TO ANYTHING ON THIS PERMIT APPLICATION. PLEASE
 CORRECT. FBC 107.2.1
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 4) THE DORMONT FLEX CONNECT IS NOT PART OF THE U.L
 LISTING OF THIS GENERATOR. CALL'S TO GENERAC ABOUT THIS
 ISSUE HAVE GONE UNANSWERED IN THE PAST WITH CALLS TO
 DORMONT SAYING THAT THIS FLEX CONNECTOR IS ONLY
 APPROVED AS LABEL. THIS SAME CONNECTED IS SUPPLIED FOR
 ALL THERE GENERATORS UP TO 42KW. THE CHART PROVIDED BY
 DORMONT WILL BE WHAT THE INSPECTOR GOES BY ON THE
 INSPECTION.
  
 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695