Plan Review Notes
Plan Review Notes For Permit 18050846
Permit Number 18050846
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-08 11:17:071ST REVIEW FBC-2014 MECHANICAL
 REVISION #18050846
 MASTER #16120880
 6/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.3.01: THE RETURN TRANSFER DUCTS FROM
 OFFICES 103A & 103B ARE UNDERSIZED PER SECTION 601.5
 (1). THE TRANSFERS MUST BE SIZED AT 1-1/2 TIMES THE
 CROSS-SECTIONAL AREAS OF THE DUCTS SUPPLYING AIR TO THE
 ROOMS. ACCORDING TO THE ORIGINAL AIR DISTRIBUTION
 SCHEDULE ON PLAN SHEET M3.00, 12" FLEX DUCTS WILL BE
 SUPPLYING AIR TO THE NEW OFFICES. PLEASE INCREASE THE
 SIZES OF THE TRANSFER DUCTS TO MEET COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER