| Plan Review Notes For Permit 18050846 |
| Permit Number |
18050846 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-08 11:17:07 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #18050846 | | | MASTER #16120880 | | | 6/8/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1.3.01: THE RETURN TRANSFER DUCTS FROM | | | OFFICES 103A & 103B ARE UNDERSIZED PER SECTION 601.5 | | | (1). THE TRANSFERS MUST BE SIZED AT 1-1/2 TIMES THE | | | CROSS-SECTIONAL AREAS OF THE DUCTS SUPPLYING AIR TO THE | | | ROOMS. ACCORDING TO THE ORIGINAL AIR DISTRIBUTION | | | SCHEDULE ON PLAN SHEET M3.00, 12" FLEX DUCTS WILL BE | | | SUPPLYING AIR TO THE NEW OFFICES. PLEASE INCREASE THE | | | SIZES OF THE TRANSFER DUCTS TO MEET COMPLIANCE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|