| Plan Review Notes For Permit 18050823 |
| Permit Number |
18050823 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-25 08:43:38 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) THERE IS NO GATE INDICATED ON THE PLAN. | | | | | | A GATE IS REQUIRED FOR FD EMERGENCY ACCESS AND 20' IN | | | THE MINIMUM CLEARANCE OF A FIRE LANE. | | | | | | PER NFPA 241 SAFEGUARDING CONSTRUCTION AND ALTERATION | | | OPERATIONS | | | | | | 7.5.5 ACCESS ROADWAYS. | | | | | | 7.5.5.1 EVERY BUILDING SHALL BE ACCESSIBLE BY FIRE | | | DEPARTMENT | | | APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER | | | DRIVING | | | SURFACE OF NOT LESS THAN 6.1 M (20 FT) OF UNOBSTRUCTED | | | WIDTH, HAVING | | | THE ABILITY TO WITHSTAND THE LIVE LOADS OF FIRE | | | APPARATUS, AND | | | HAVING A MINIMUM OF 4.1 M (13 FT 6 IN.) OF VERTICAL | | | CLEARANCE. | | | | | | 7.5.5.2 ACCESS FOR USE OF FIRE DEPARTMENT APPARATUS | | | SHALL BE | | | PROVIDED TO THE IMMEDIATE JOB SITE AT THE START OF THE | | | PROJECT | | | AND MAINTAINED UNTIL COMPLETION. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|