| Plan Review Notes For Permit 18050811 |
| Permit Number |
18050811 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-07-11 06:37:21 | 1) THERE ARE TWO DIFFERENT GAS DRAWINGS SUBMITTED IN | | | THIS PACKAGE. REMOVE ALL OLD DRAWINGS/DOCUMENTS AND | | | COMPILE THE DOCUMENTS INTO TWO COMPLETE SETS OF PLANS | | | FOR REVIEW. WPB AMEND. TO FBC SEC.107.1. 2ND REQUEST. | | | 2) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED | | | A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER | | | BUILDING OPENINGS. THE SURVEY SHOWS 5 FEET. 2017 | | | FBC-MECH. SEC.501.3.1 & MANUF. INSTALLATION MANUAL.3RD | | | REQUEST. | | | 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A | | | NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING | | | TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE | | | USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE | | | 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES | | | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. 2ND | | | REQUEST. | | | 4) INDICATE THE ORIFICE SIZE ON THE REGULATOR SPECS SO | | | THE ALLOWABLE BTU LOAD OF THE REGULATOR CAN BE CHECKED | | | AGAINST THE BTU LOAD OF THE APPLIANCE/EQUIPMENT | | | CONNECTED.2ND REQUEST. | | | 5) THE NEW GAS DRAWING SHOWS AN EXISTING GAS METER AND | | | THE SURVEY SHOWS A NEW GAS METER. WHICH IS IT? EXISTING | | | CITY RECORDS DO NOT SHOW ANY PREVIOUS GAS SYSTEM AT | | | THIS ADDRESS. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|