| Date |
Text |
| 2018-11-05 12:55:40 | 4TH REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050807 |
| | 11/5/18 |
| | |
| | CODES IN EFFECT: |
| | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | ON MONDAY, NOVEMBER 5, IN AN EFFORT TO HELP EXPEDITE |
| | THE APPROVAL OF THE PLANS, I HAD A TELEPHONE |
| | CONVERSATION WITH THE NEW MECHANICAL ENGINEER OF RECORD |
| | JOHN D. BUEROSSE. IN THAT CONVERSATION MR. BUEROSSE |
| | ACKNOWLEDGED THAT HE HAD NOT RECEIVED THE SUBMITTED USP |
| | GUIDLINES FOR THE CLEAN ROOM FACILITY, OR THE MSDS |
| | SHEETS FOR THE HAZARDOUS CHEMICALS THAT WILL BE USED IN |
| | THE MAKING OF THE PHARMACEUTICALS IN THE CLEAN ROOM. HE |
| | ALSO ACKNOWLEDGED THE CURRENT MECHANICAL DESIGN IS |
| | DEFICIENT AND WILL HAVE TO BE MODIFIED TO BE COMPLIANT |
| | WITH THE GUIDELINES AND THE MECHANICAL CODE. AS A |
| | RESULT, I HAVE EMAILED COPIES OF THE GUIDLEINES, MSDS |
| | SHEETS, AND OTHER SUBMITTED INFORMATION. PLEASE CONTACT |
| | MR. BUEROSSE AND SUBMIT TO HIM ALL OTHER SPEC SHEETS |
| | AND PERTINENT INFRMATION SO THAT HE CAN PROVIDE A |
| | CODE-COMPLIANT MECHANICAL DESIGN AS SOON AS POSSIBLE. |
| | |
| | PRINTED BELOW ARE THE REPEATED COMMENTS THAT STILL MUST |
| | BE ADDRESSED, AND SOME ADDITIONAL COMMENTS. |
| | |
| | 1) SHEET M-1: CLARIFY HOW THE ROOM PRESSURIZATIONS AND |
| | HEPA FILTERING SYSTEMS FOR THE CLEAN ROOMS WERE |
| | DESIGNED - UNDER WHICH GUIDELINES, STANDARD OR CODE, |
| | AND PROVIDE CALCULATIONS AND A SUPPLEMENTAL VENTILATION |
| | TABLE THAT INDICATES THE PRESSURE RELATIONSHIPS AND |
| | REQUIRED AIR CHANGES PER HOUR FOR EACH ROOM. |
| | |
| | 2) A2: SUBMIT SHOP DRAWINGS FOR THE PREFAB CLEAN ROOM |
| | REVIEWED AND APPROVED BY THE EOR. PLEASE NOTE THAT |
| | SPECILIZED MECHANICAL SYSTEMS THAT INVOLVE TOXIC AIR |
| | FILTRATION MUST BE DESIGNED BY A FL. LICENSED ENGINEER |
| | IF THE INSTALLATION OF THE SYSTEMS EXCEED A COST VALUE |
| | OF $5000.00- SECTION 105.3.1.2(4) WPB. PLEASE PROVIDE A |
| | COST BREAKDOWN FOR THE PROPOSED FACILITY THAT INCLUDES |
| | LABOR, MATERIALS, EQUIPMENT, FIXTURES, APPLIANCES, |
| | DESIGN FEES, PROFIT AND OVERHEAD- SECTION 109.3 WPB. |
| | |
| | 3) M-1: THE FRESH AIR CALCULATION FOR THE PHARMACY |
| | SHALL BE IN ACCORDANCE WTH TABLE 403.3.1.1 FBC M WHICH |
| | REQUIRES A RATE BASED ON 10, NOT 5 PEOPLE PER 1000 SF- |
| | PLEASE CORRECT. |
| | |
| | 4) M-1: PROVIDE AN AIR DEVICE SCHEDULE THAT INCLUDES |
| | THE HEPA FILTERS, THE IRIS VOLUME DAMPERS, THE MIXING |
| | BOX, THE SUPPLY DIFFUSERS, AND RETURN GRILLS. SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE FILTERS, THE |
| | DAMPERS, AND THE MIXING BOX APPROVED AND STAMPED BY THE |
| | EOR. |
| | |
| | 5) M-1 & A3: SHOW THE LOCATION OF THE BIOSAFETY |
| | CABINET, THE EXHAUST DUCT RUN, AND THE EXHAUST |
| | TERMINATION LOCATION. INDICATE THE TYPE OF EXHAUST DUCT |
| | WORK AND TERMINATION CAP TO BE INSTALLED. THE SUBMITTED |
| | SPEC SHEETS FOR THE CABINET, AND ADDITIONAL SPEC SHEETS |
| | FOR THE EXHAUST SYSTEM SHALL BE APPROVED AND STAMPED BY |
| | THE EOR, ALONG WITH ANY OTHER SPECILIZED EQUIPMENT TO |
| | BE INSTALLED IN THE CLEAN ROOMS. |
| | |
| | 6) PROVIDE A LIST OF CHEMICALS AND MATERIALS TO BE |
| | STORED AT THE FACILTY AND THEIR QUANTITIES, AND SUBMIT |
| | MSDS SHEETS. REFER TO SECTIONS 510.1 FBC M AND PROVIDE |
| | A NARRATIVE DESCRIPTION OF THE PROCESSES TO BE |
| | CONDUCTED IN THE FACILITY. PLEASE NOTE THAT IF THE |
| | FACILITY IS DETERMINED TO BE A LABORATORY, A EXHAUST |
| | SYSTEM WITH A RATE OF 1.0 CFMS PER SF. SHALL BE |
| | PROVIDED- TABLE 403.3.1.1 |
| | |
| | FBC M. |
| | |
| | 7) BASED ON THE NEWLY SUBMITTED USP GUIDELINES FOR THE |
| | CLEAN ROOM, THE MSDS SHEETS AND EQUIPMENT SPECS, IN |
| | ORDER TO MAINTAIN THE REQUIRED NEGATIVE PRESSURE IN THE |
| | SPACE, AN EXHAUST VENTILATION SYSTEM MUST BE INSTALLED. |
| | PLEASE REFER TO THE GUIDELINES FOR REQUIRED EXHAUST |
| | RATE AND REQUIRED AIR CHANGES PER HOUR. |
| | |
| | 8) SHEET A3: PLEASE VERIFY THERE IS A MINIMUIM 42" HIGH |
| | GUARD OR PARAPET ON THE ROOF EDGE IN THE AREA OF THE |
| | GENERATOR- SEE SECTION 304.11 FBC M. (THE REVISED SHEET |
| | A3 NOW SHOWS A "REMOVABLE" GUARD RAIL WHICH MUST BE |
| | PERMANENTLY INSTALLED. PROVIDE INSTALLATION DETAILS). |
| | |
| | 9) A3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE GENERATOR SUPPORT FRAME, AND |
| | ATTACHMENT OF THE GENERATOR TO THE FRAME- SEE SECTION |
| | 1609 FBC BC. (THE GENERATOR IS NOW DESIGNATED AS A |
| | "FUTURE INSTALLATION" ). |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR, AND SHOW THE DISCHARGE LOCATION OF THE |
| | GENERATOR EXHAUST ON THE PLAN- SEE SECTION 501.3.1 FBC |
| | M. (THE GENERATOR IS NOW DESGINATED AS A "FUTURE |
| | INSTALLATION"). |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |