| Date |
Text |
| 2018-10-25 18:00:28 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050807 |
| | 10/2518 |
| | |
| | CODES IN EFFECT: |
| | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | PRINTED BELOW ARE THE 2ND REVIEW COMMENTS THAT STILL |
| | EXIST ON THE PROPOSED MECHANICAL PLAN SUBMITTAL FOR THE |
| | PROJECT. THESE COMMENTS WERE DISCUSSED IN LENGTH AT A |
| | MEETING HERE AT THE DEVELOPMENT SERVICES CONFERENCE |
| | ROOM AT 10:00 AM, MONDAY, SEPTEMBER 17, 2018. PRESENT |
| | AT THAT MEETING WERE THE PLANS EXAMNIERS, THE |
| | CONTRACTOR, THE ARCHITECT, REPRESENTATIVES OF THE |
| | OWNERSHIP OF THE COMPANY. CONCERNING THE MECHANICAL, IT |
| | WAS STATED THAT THE PLANS AND CALCULATIONS WOULD BE |
| | CORRECTED AND SUBMITTED ALONG WITH THE REQUESTED SHOP |
| | DRAWINGS, AND MANUFACTURER'S PRODUCT SPEC SHEETS FOR |
| | ALL MECHANICAL COMPONENTS AND EQUIPMENT. AS A RESULT, |
| | THE PLANS THAT HAVE BEEN SUBMITTED ON THIS 3RD REVIEW |
| | ARE ILLEGIBLE COPIES OF THE PREVIOUS PLANS WHICH NOW |
| | BEAR A COPIED TITLE BLOCK OF JOHN D. BUEROSE PE. MR. |
| | BUEROSE'S ORIGINAL SIGNATURE AND SEAL, AS REQUIRED BY |
| | FLORIDA STATUTE AND FAC, IS NOT ON THE PLANS. PLEASE |
| | NOTE THAT NO RESPONSE NARRATIVE WAS PROVIDED TO ADDRESS |
| | THE MECHANICAL COMMENTS WHICH WAS REQUESTED IN AN |
| | EFFORT TO HELP EXPEDITE THE PLAN APPROVAL PROCESS. UPON |
| | RECEIPT OF THESE COMMENTS PLEASE HAVE THE NEW ENGINEER |
| | MR. BUEROSE CONTACT ME SO THAT THE ISSUES CAN BE |
| | RESOLVED AND COMPLIANT PLANS CAN BE RESUBMITTED. |
| | |
| | 1) SHEET M-1: CLARIFY HOW THE ROOM PRESSURIZATIONS AND |
| | HEPA FILTERING SYSTEMS FOR THE CLEAN ROOMS WERE |
| | DESIGNED - UNDER WHICH GUIDELINES, STANDARD OR CODE, |
| | AND PROVIDE CALCULATIONS AND A SUPPLEMENTAL VENTILATION |
| | TABLE THAT INDICATES THE PRESSURE RELATIONSHIPS AND |
| | REQUIRED AIR CHANGES PER HOUR FOR EACH ROOM. |
| | |
| | 2) A2: SUBMIT SHOP DRAWINGS FOR THE PREFAB CLEAN ROOM |
| | REVIEWED AND APPROVED BY THE EOR. PLEASE NOTE THAT |
| | SPECILIZED MECHANICAL SYSTEMS THAT INVOLVE TOXIC AIR |
| | FILTRATION MUST BE DESIGNED BY A FL. LICENSED ENGINEER |
| | IF THE INSTALLATION OF THE SYSTEMS EXCEED A COST VALUE |
| | OF $5000.00- SECTION 105.3.1.2(4) WPB. PLEASE PROVIDE A |
| | COST BREAKDOWN FOR THE PROPOSED FACILITY THAT INCLUDES |
| | LABOR, MATERIALS, EQUIPMENT, FIXTURES, APPLIANCES, |
| | DESIGN FEES, PROFIT AND OVERHEAD- SECTION 109.3 WPB. |
| | |
| | 3) M-1: THE FRESH AIR CALCULATION FOR THE PHARMACY |
| | SHALL BE IN ACCORDANCE WTH TABLE 403.3.1.1 FBC M WHICH |
| | REQUIRES A RATE BASED ON 10, NOT 5 PEOPLE PER 1000 SF- |
| | PLEASE CORRECT. |
| | |
| | 4) M-1: PROVIDE AN AIR DEVICE SCHEDULE THAT INCLUDES |
| | THE HEPA FILTERS, THE IRIS VOLUME DAMPERS, THE MIXING |
| | BOX, THE SUPPLY DIFFUSERS, AND RETURN GRILLS. SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE FILTERS, THE |
| | DAMPERS, AND THE MIXING BOX APPROVED AND STAMPED BY THE |
| | EOR. |
| | |
| | 5) M-1 & A3: SHOW THE LOCATION OF THE BIOSAFETY |
| | CABINET, THE EXHAUST DUCT RUN, AND THE EXHAUST |
| | TERMINATION LOCATION. INDICATE THE TYPE OF EXHAUST DUCT |
| | WORK AND TERMINATION CAP TO BE INSTALLED. THE SUBMITTED |
| | SPEC SHEETS FOR THE CABINET, AND ADDITIONAL SPEC SHEETS |
| | FOR THE EXHAUST SYSTEM (NOT PROVIDED), SHALL BE |
| | APPROVED AND STAMPED BY THE EOR, ALONG WITH ANY OTHER |
| | SPECILIZED EQUIPMENT TO BE INSTALLED IN THE CLEAN |
| | ROOMS. |
| | |
| | 6) PROVIDE A LIST OF CHEMICALS AND MATERIALS TO BE |
| | STORED AT THE FACILTY AND THEIR QUANTITIES, AND SUBMIT |
| | MSDS SHEETS. REFER TO SECTIONS 510.1 FBC M AND PROVIDE |
| | A NARRATIVE DESCRIPTION OF THE PROCESSES TO BE |
| | CONDUCTED IN THE FACILITY. PLEASE NOTE THAT IF THE |
| | FACILITY IS DETERMINED TO BE A LABORATORY, A EXHAUST |
| | SYSTEM WITH A RATE OF 1.0 CFMS PER SF. SHALL BE |
| | PROVIDED- TABLE 403.3.1.1 FBC M. |
| | |
| | 7) SHEET A3: PLEASE VERIFY THERE IS A MINIMUIM 42" HIGH |
| | GUARD OR PARAPET ON THE ROOF EDGE IN THE AREA OF THE |
| | GENERATOR- SEE SECTION 304.11 FBC M. |
| | |
| | 8) A3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE GENERATOR SUPPORT FRAME, AND |
| | ATTACHMENT OF THE GENERATOR TO THE FRAME- SEE SECTION |
| | 1609 FBC BC. |
| | |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR, AND SHOW THE DISCHARGE LOCATION OF THE |
| | GENERATOR EXHAUST ON THE PLAN- SEE SECTION 501.3.1 FBC |
| | M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |