Plan Review Notes
Plan Review Notes For Permit 18050807
Permit Number 18050807
Review Stop M
Sequence Number 3
Notes
Date Text
2018-10-25 18:00:282ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18050807
 10/2518
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PRINTED BELOW ARE THE 2ND REVIEW COMMENTS THAT STILL
 EXIST ON THE PROPOSED MECHANICAL PLAN SUBMITTAL FOR THE
 PROJECT. THESE COMMENTS WERE DISCUSSED IN LENGTH AT A
 MEETING HERE AT THE DEVELOPMENT SERVICES CONFERENCE
 ROOM AT 10:00 AM, MONDAY, SEPTEMBER 17, 2018. PRESENT
 AT THAT MEETING WERE THE PLANS EXAMNIERS, THE
 CONTRACTOR, THE ARCHITECT, REPRESENTATIVES OF THE
 OWNERSHIP OF THE COMPANY. CONCERNING THE MECHANICAL, IT
 WAS STATED THAT THE PLANS AND CALCULATIONS WOULD BE
 CORRECTED AND SUBMITTED ALONG WITH THE REQUESTED SHOP
 DRAWINGS, AND MANUFACTURER'S PRODUCT SPEC SHEETS FOR
 ALL MECHANICAL COMPONENTS AND EQUIPMENT. AS A RESULT,
 THE PLANS THAT HAVE BEEN SUBMITTED ON THIS 3RD REVIEW
 ARE ILLEGIBLE COPIES OF THE PREVIOUS PLANS WHICH NOW
 BEAR A COPIED TITLE BLOCK OF JOHN D. BUEROSE PE. MR.
 BUEROSE'S ORIGINAL SIGNATURE AND SEAL, AS REQUIRED BY
 FLORIDA STATUTE AND FAC, IS NOT ON THE PLANS. PLEASE
 NOTE THAT NO RESPONSE NARRATIVE WAS PROVIDED TO ADDRESS
 THE MECHANICAL COMMENTS WHICH WAS REQUESTED IN AN
 EFFORT TO HELP EXPEDITE THE PLAN APPROVAL PROCESS. UPON
 RECEIPT OF THESE COMMENTS PLEASE HAVE THE NEW ENGINEER
 MR. BUEROSE CONTACT ME SO THAT THE ISSUES CAN BE
 RESOLVED AND COMPLIANT PLANS CAN BE RESUBMITTED.
  
 1) SHEET M-1: CLARIFY HOW THE ROOM PRESSURIZATIONS AND
 HEPA FILTERING SYSTEMS FOR THE CLEAN ROOMS WERE
 DESIGNED - UNDER WHICH GUIDELINES, STANDARD OR CODE,
 AND PROVIDE CALCULATIONS AND A SUPPLEMENTAL VENTILATION
 TABLE THAT INDICATES THE PRESSURE RELATIONSHIPS AND
 REQUIRED AIR CHANGES PER HOUR FOR EACH ROOM.
  
 2) A2: SUBMIT SHOP DRAWINGS FOR THE PREFAB CLEAN ROOM
 REVIEWED AND APPROVED BY THE EOR. PLEASE NOTE THAT
 SPECILIZED MECHANICAL SYSTEMS THAT INVOLVE TOXIC AIR
 FILTRATION MUST BE DESIGNED BY A FL. LICENSED ENGINEER
 IF THE INSTALLATION OF THE SYSTEMS EXCEED A COST VALUE
 OF $5000.00- SECTION 105.3.1.2(4) WPB. PLEASE PROVIDE A
 COST BREAKDOWN FOR THE PROPOSED FACILITY THAT INCLUDES
 LABOR, MATERIALS, EQUIPMENT, FIXTURES, APPLIANCES,
 DESIGN FEES, PROFIT AND OVERHEAD- SECTION 109.3 WPB.
  
 3) M-1: THE FRESH AIR CALCULATION FOR THE PHARMACY
 SHALL BE IN ACCORDANCE WTH TABLE 403.3.1.1 FBC M WHICH
 REQUIRES A RATE BASED ON 10, NOT 5 PEOPLE PER 1000 SF-
 PLEASE CORRECT.
  
 4) M-1: PROVIDE AN AIR DEVICE SCHEDULE THAT INCLUDES
 THE HEPA FILTERS, THE IRIS VOLUME DAMPERS, THE MIXING
 BOX, THE SUPPLY DIFFUSERS, AND RETURN GRILLS. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE FILTERS, THE
 DAMPERS, AND THE MIXING BOX APPROVED AND STAMPED BY THE
 EOR.
  
 5) M-1 & A3: SHOW THE LOCATION OF THE BIOSAFETY
 CABINET, THE EXHAUST DUCT RUN, AND THE EXHAUST
 TERMINATION LOCATION. INDICATE THE TYPE OF EXHAUST DUCT
 WORK AND TERMINATION CAP TO BE INSTALLED. THE SUBMITTED
 SPEC SHEETS FOR THE CABINET, AND ADDITIONAL SPEC SHEETS
 FOR THE EXHAUST SYSTEM (NOT PROVIDED), SHALL BE
 APPROVED AND STAMPED BY THE EOR, ALONG WITH ANY OTHER
 SPECILIZED EQUIPMENT TO BE INSTALLED IN THE CLEAN
 ROOMS.
  
 6) PROVIDE A LIST OF CHEMICALS AND MATERIALS TO BE
 STORED AT THE FACILTY AND THEIR QUANTITIES, AND SUBMIT
 MSDS SHEETS. REFER TO SECTIONS 510.1 FBC M AND PROVIDE
 A NARRATIVE DESCRIPTION OF THE PROCESSES TO BE
 CONDUCTED IN THE FACILITY. PLEASE NOTE THAT IF THE
 FACILITY IS DETERMINED TO BE A LABORATORY, A EXHAUST
 SYSTEM WITH A RATE OF 1.0 CFMS PER SF. SHALL BE
 PROVIDED- TABLE 403.3.1.1 FBC M.
  
 7) SHEET A3: PLEASE VERIFY THERE IS A MINIMUIM 42" HIGH
 GUARD OR PARAPET ON THE ROOF EDGE IN THE AREA OF THE
 GENERATOR- SEE SECTION 304.11 FBC M.
  
 8) A3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE GENERATOR SUPPORT FRAME, AND
 ATTACHMENT OF THE GENERATOR TO THE FRAME- SEE SECTION
 1609 FBC BC.
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, AND SHOW THE DISCHARGE LOCATION OF THE
 GENERATOR EXHAUST ON THE PLAN- SEE SECTION 501.3.1 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved