Plan Review Notes
Plan Review Notes For Permit 18050807
Permit Number 18050807
Review Stop P
Sequence Number 2
Notes
Date Text
2018-08-21 08:57:132ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH
 2ND REQUEST.
  
 1. BY CONNECTING THE TWO BAYS YOU HAVE INCREASED YOUR
 OCCUPANT LOAD IF THERE IS NOT AN EXISTING WATER
 FOUNTAIN OR SERVICE SINK A NEW ONE SHALL BE PROVIDED.
 PER FBC PL TABLE 403.1
 PROVIDE PLAN SHOWING EXISTING.
  
 2. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC FOR
 NEW SINK PLUMBING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 NEW COMMENT:
  
 1. THE APPLICATION IS CALLING OUT UNIT 217 BUT PLANS
 SHOW UNITS 214 + 215 PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  