| Plan Review Notes For Permit 18050807 |
| Permit Number |
18050807 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-08-21 09:34:47 | 2NDREVIEW: FBC 2017 6TH EDITION | | | | | | GAS COMMENTS: | | | | | | 1. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS REGULATOR'S VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | 2ND REQUEST 2. HOW WILL THE MIRO INDUSTRIES PIPE | | | SUPPORT BE ATTACHED TO THE ROOF PLEASE SPECIFY. PER WPB | | | AMEND 107.2.1 | | | | | | 2ND REQUEST 3. ONE OF THE SIZING TABLES LISTED ON THE | | | PLAN 402.4(8) IS FOR NATURAL GAS COPPER TUBING PLEASE | | | CLARIFY. PER WPB AMEND 107.2.1 ALSO PROVIDE SIZING FOR | | | PIPING DOWN STREAM OF .5LB REGULATOR | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|