Plan Review Notes
Plan Review Notes For Permit 18050807
Permit Number 18050807
Review Stop G
Sequence Number 2
Notes
Date Text
2018-08-21 09:34:472NDREVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS:
  
 1. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS REGULATOR'S VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 2ND REQUEST 2. HOW WILL THE MIRO INDUSTRIES PIPE
 SUPPORT BE ATTACHED TO THE ROOF PLEASE SPECIFY. PER WPB
 AMEND 107.2.1
  
 2ND REQUEST 3. ONE OF THE SIZING TABLES LISTED ON THE
 PLAN 402.4(8) IS FOR NATURAL GAS COPPER TUBING PLEASE
 CLARIFY. PER WPB AMEND 107.2.1 ALSO PROVIDE SIZING FOR
 PIPING DOWN STREAM OF .5LB REGULATOR
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  