Plan Review Notes
Plan Review Notes For Permit 18050807
Permit Number 18050807
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-21 18:17:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. REVISE PLAN TO SHOW 18" CLEARANCE PULL SIDE AND 12"
 PUSH SIDE (IF THE DOOR HAS A CLOSER AND A LATCH)
 REQUIRED BY FBC A 404.2.4.1(A) AND (C).
  
 2ND REVIEW, SAME PLAN SUBMITTED. DOORS APPEAR TO HAVE
 AN OBSTRUCTION WHICH BLOCKS THE CLEARANCE.
  
 2. OK
  
 3. REVISE PLAN TO INCLUDE EXISTING OCCUPANCY
 CLASSIFICATION. IF THIS IS A CHANGE OF OCCUPANCY,
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER 10.
  
  
  