| Plan Review Notes For Permit 18050807 |
| Permit Number |
18050807 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-08-21 18:17:20 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1. REVISE PLAN TO SHOW 18" CLEARANCE PULL SIDE AND 12" | | | PUSH SIDE (IF THE DOOR HAS A CLOSER AND A LATCH) | | | REQUIRED BY FBC A 404.2.4.1(A) AND (C). | | | | | | 2ND REVIEW, SAME PLAN SUBMITTED. DOORS APPEAR TO HAVE | | | AN OBSTRUCTION WHICH BLOCKS THE CLEARANCE. | | | | | | 2. OK | | | | | | 3. REVISE PLAN TO INCLUDE EXISTING OCCUPANCY | | | CLASSIFICATION. IF THIS IS A CHANGE OF OCCUPANCY, | | | REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER 10. | | | | | | | | | |
|