2018-05-23 07:51:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 2. IT APPEARS THE SERVICE TO THE BUILDING IS 3 PHASE,
 120/208 VOLT. THE RISER DIAGRAM IS SHOWING THE PANEL TO
 THE UNIT AS SINGLE PHASE 120/208. IF IT IS A SINGLE
 PHASE SERVICE, THE LOAD CALCULATION PROVIDED EXCEEDS
 THE VALUE OF THE DISCONNECT, TRANSFER SWITCH, FEEDER
 AND POSSIBLY THE METER. ADDITIONALLY, THE FACTOR FOR
 CONTINUOUS LOAD IS NOT INCLUDED. PROVIDE CORRECTION AND
 ACCURATE LOAD CALCULATION. NEC 220
 3. PROVIDE SPEC SHEET FOR TRANSFER SWTICH. NEC 110.3;
 WPB FBC 107.2.1
 4. IT APPEARS THAT THE GENERATOR WILL BE OVERLOADED. I
 HAVE NOT BEEN ABLE TO FIND A MANUFACTURER THAT MAKES A
 SINGLE PHASE 120/208 GENERATOR. WILL A THREE PHASE
 GENERATOR WILL BE USED AS A SINGLE PHASE SOURCE? A
 THREE PHASE GENERATOR WOULD HAVE AN OUTPUT OF
 APPROXIMATELY 61 AMPS. A SINGLE PHASE GENERATOR HAS A
 VOLTAGE OF 120/240, WHICH WOULD NOT BE COMPATIBLE WITH
 THIS SYSTEM. PROVIDE CLARIFICATION AND GENERATOR SPEC
 SHEETS. NEC 110.3, 110.4; WPB FBC 107.2.1
 5. PROVIDE CLARIFICATION FOR CIRCUITS 9A, 9B, 11A, AND
 11B. WHAT TYPE OF EQUIPMENT IS PLUGGING INTO THESE
 DEDICATED OUTLETS? PANEL SCHEDULE SHOWS A LOAD OF .4KW.
 PROVIDE SPEC SHEETS FOR THIS EQUIPMENT. NEC 110.3; WPB
 FBC 107.2.1
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  