2018-06-18 16:37:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENT NOT ADDRESSED SATISFACTORILY. PREVIOUS
 COMMENTS THAT HAVE BEEN ADDRESSED SATISFACTORILY HAVE
 BEEN NOTED AS CORRECTED. ITEMS REMAINING HAVE FURTHER
 COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). NEC 215.5, 230, 408.30 (COMMENT RESPONSE
 STATES THAT THIS IS AN EXISTING SERVICE. I UNDERSTAND
 THAT, BUT STILL REQUIRE A RISER DIAGRAM WHICH WILL SHOW
 WHAT THE SIZE OF THE EXISTING SERVICE. THERE IS NOTHING
 IN THE PLAN TO INDICATE THE CURRENT SERVICE SIZE.
 PROVIDE AS PREVIOUSLY CORRECTED.)
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (THE LOAD
 CALCULATION FOR THE UNIT WAS SUPPLIED, BUT I STILL NEED
 THE LOAD CALCULATION FOR THE RISER/SERVICE THAT
 SUPPLIES THIS UNIT. AS MANY LARGE BUILDINGS HAVE A
 SERVICE SIZED FOR TANK TYPE WATER HEATERS, INSTALLING
 TANKLESS UNITS WITH HIGH DEMAND CAN OVERLOAD THE
 SYSTEM. THIS LOAD CALCULATION IS REQUIRED. PROVIDE AS
 REQUESTED.)
 4. PROVIDE AFCI PROTECTION FOR ANY MODIFIED CIRCUITS
 PER NEC 210.12(B). (COMMENT REAPOSE STATES THAT AFCI
 PROTECTION IS NOTED ON DRAWING, BUT THIS HAS NOT BEEN
 INCLUDED AS REQUESTED. PROVIDE CORRECTION.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  