Plan Review Notes
Plan Review Notes For Permit 18050787
Permit Number 18050787
Review Stop B
Sequence Number 2
Notes
Date Text
2018-06-19 12:14:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROFLEX MAXXIM SIM90 ASTM E90 TEST REPORT WAS
 PROVIDED, BUT IT WAS TESTED WITH AN 8" SLAB AND DROPPED
 GYPSUM CEILING. SLAB THICKNESS FOR THIS BUILDING IS NOT
 KNOWN; CONFIRM IT IS 8" IF YOU WISH TO UTILIZE AN 8"
 TEST REPORT. DROPPED CEILING NOT ACCEPTABLE.
  
 PROFLEX RCU500 ASTM E492 TEST REPORT (IIC) SUBMITTED;
 THIS TEST REPORT IS ACCEPTABLE.
  
 FIRST SUBMITTAL PROVIDED SPEC SHEETS FOR PROFLEX MSC.
  
 SINCE TWO DIFFERENT TEST REPORTS AND A DIFFERENT SPEC
 SHEET WERE PROVIDED (THREE DIFFERENT PRODUCTS), IT IS
 NOT CLEAR WHAT PRODUCT IS PROPOSED. STC, IIC, FLAME
 SPREAD ARE REQUIRED. SELECT THE ONE PRODUCT YOU WISH TO
 PROPOSE AND PROVIDE THE THREE TEST REPORTS AS NOTED IN
 COMMENT #2.
  
 2. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
  