Plan Review Notes
Plan Review Notes For Permit 18050779
Permit Number 18050779
Review Stop B
Sequence Number 1
Notes
Date Text
2018-05-25 08:10:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 GENERATOR PAD AND ANCHORING
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC 107.2.1.2 PROVIDE INSTALLATION GUIDE FOR THE
 GENERATOR. SEE NOTE NUMBER 1 ON SHEET 6 OF 11 GENERAC
 INSTALLATION LAYOUT. THE MINIMUM RECOMMENDED CONCRETE
 PAD SIZE IS 43" X 74.2".
  
 3) FBC 107.2.1 SPECIFY THE REQUIRED EMBED DEPTH OF THE
 3/8" DIAMETER CONCRETE ANCHORS.
  
 4) FBC 301.2.1 SPECIFY THE WIND SPEED DATA ON THE
 GENERATOR PAD PLANS.
  