| Plan Review Notes For Permit 18050779 |
| Permit Number |
18050779 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-25 08:10:25 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | GENERATOR PAD AND ANCHORING | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) FBC 107.2.1.2 PROVIDE INSTALLATION GUIDE FOR THE | | | GENERATOR. SEE NOTE NUMBER 1 ON SHEET 6 OF 11 GENERAC | | | INSTALLATION LAYOUT. THE MINIMUM RECOMMENDED CONCRETE | | | PAD SIZE IS 43" X 74.2". | | | | | | 3) FBC 107.2.1 SPECIFY THE REQUIRED EMBED DEPTH OF THE | | | 3/8" DIAMETER CONCRETE ANCHORS. | | | | | | 4) FBC 301.2.1 SPECIFY THE WIND SPEED DATA ON THE | | | GENERATOR PAD PLANS. | | | |
|