| Plan Review Notes For Permit 18050756 |
| Permit Number |
18050756 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-31 11:44:30 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR. 2017 FBCR SEC. G2422.1 (8). | | | 2) THE CONTRACT STATES THAT 80 FEET OF PIPE WILL BE | | | INSTALLED BUT THE SURVEY AND GAS DRAWING STATES 50 FEET | | | OF PIPE. CLARIFY. | | | 3) SHOW THE TYPE OF EXISTING PIPE TO THE POOL HEATER | | | AND THE COOKTOP. | | | 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE FOR | | | THE LOW PRESSURE GAS SYSTEM. | | | 5) THE SHUTOFF VALVE AT THE GENERATOR SHALL BE UPSTREAM | | | OF THE REGULATOR. | | | 6) MEDIUM PRESSURE REGULATORS ARE REQUIRED AT THE POOL | | | HEATER AND THE COOKTOP. | | | 7) SHOW THE TYPE OF MATERIAL FOR ALL PIPING ON THE GAS | | | PLAN. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|