Plan Review Notes
Plan Review Notes For Permit 18050756
Permit Number 18050756
Review Stop G
Sequence Number 1
Notes
Date Text
2018-05-31 11:44:301) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 2) THE CONTRACT STATES THAT 80 FEET OF PIPE WILL BE
 INSTALLED BUT THE SURVEY AND GAS DRAWING STATES 50 FEET
 OF PIPE. CLARIFY.
 3) SHOW THE TYPE OF EXISTING PIPE TO THE POOL HEATER
 AND THE COOKTOP.
 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE FOR
 THE LOW PRESSURE GAS SYSTEM.
 5) THE SHUTOFF VALVE AT THE GENERATOR SHALL BE UPSTREAM
 OF THE REGULATOR.
 6) MEDIUM PRESSURE REGULATORS ARE REQUIRED AT THE POOL
 HEATER AND THE COOKTOP.
 7) SHOW THE TYPE OF MATERIAL FOR ALL PIPING ON THE GAS
 PLAN.
  