2018-05-31 06:47:021) SHOW THE LOCATION OF THE MEDIUM-PRESSURE REGULATOR
 ON THE GAS DRAWING.
 2) SHOW THE SIZE & TYPE OF PIPE DOWWNSTREAM OF THE
 MEDIUM-PRESSURE REGULATOR ON THE GAS PLAN.
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE
 USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THE LOW PRESSURE GAS SYSTEM.
 REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8,
 402.3, AND TABLES 402.4 (1) THRU 402.4 (37) OR 2017
 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2, &
 G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW