Plan Review Notes
Plan Review Notes For Permit 18050715
Permit Number 18050715
Review Stop G
Sequence Number 1
Notes
Date Text
2018-05-19 08:26:57 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE
 EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH
 GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND
 PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR
 SEC.G2415.9, G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION SHEETS FOR THE REGULATOR. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2017 FBCR
 SEC.G2421.1, FBC-FUEL GAS SEC. 410.1.
 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
 10) THE EXISTING BTU LOAD LISTED ON THE GAS DRAWING
 DOES NOT CORRELATE WITH THE EXISTING GAS PLAN ON FILE
 WITH THE CITY. I HAVE PLACED A COPY OF THE GAS DRAWING
 FROM THE ORIGINAL PERMIT #01090269.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  