| | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF |
| | THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE |
| | EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH |
| | GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND |
| | PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR |
| | SEC.G2415.9, G2415.11. |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL |
| | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| | GENERATOR. 2017 FBCR SEC. G2422.1 (8). |
| | 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 |
| | FBCR SEC.G2419.4. |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION SHEETS FOR THE REGULATOR. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION. 2017 FBCR |
| | SEC.G2421.1, FBC-FUEL GAS SEC. 410.1. |
| | 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE |
| | CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. |
| | TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1. |
| | 10) THE EXISTING BTU LOAD LISTED ON THE GAS DRAWING |
| | DOES NOT CORRELATE WITH THE EXISTING GAS PLAN ON FILE |
| | WITH THE CITY. I HAVE PLACED A COPY OF THE GAS DRAWING |
| | FROM THE ORIGINAL PERMIT #01090269. |
| | |
| | |