2018-07-31 10:21:551) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 AN EXISTING 1 1/2 INCH GALVANIZED LINE AT THE OUTLET OF
 THE GAS METER AND THE SUBMITTED GAS PLAN FROM RELIABLE
 POWER SYSTEMS SHOWS AN EXISTING 3/4 INCH LINE. CLARIFY.
 2) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 AN EXISTING 1 INCH LINE TO THE INTERIOR OF THE
 STRUCTURE AND THE SUBMITTED GAS PLAN FROM RELIABLE
 POWER SYSTEMS SHOWS A 3/4 INCH LINE. CLARIFY.
 3) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS SHOWS
 A FUTURE BBQ GRILL AT 55,000 BTU'S. THIS APPLIANCE MUST
 BE ADDED TO THE EXISTING LOAD . 2017 FBC-FUEL GAS
 SEC.401.4.
 4) THE EXISTING GAS PLAN SHOWS AN 1 1/4 INCH PE LINE TO
 THE POOL HEATER AND BBQ AT A DISTANCE OF 83 FEET. THIS
 DISTANCE SHALL BE USED FOR THE SIZING OF THE 2 PSI
 SYSTEM. 2017 FBC-FUEL GAS SEC.402.4.1.
  
 NOTE: I HAVE PLACED A COPY OF THE EXISTING GAS PLAN IN
 YOUR APPLICATION THAT YOU CAN USE AS A REFERENCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  