 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING
 THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE BTU LOAD OF THE RANGE DOES NOT CORRELATE WITH
 THE BTU LOAD SHOWN UNDER PERMIT # 17111114. I HAVE
 INCLUDED A COPY IN YOUR APPLICATION FILE TO BE USED AS
 REFERENCE.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 5) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 6) THE LONGEST RUN THAT IS LISTED ON THE GAS DRAWING
 DOES NOT CORRELATE WITH THE ORIGINAL GAS PERMIT.SEE THE
 COPY OF THE ORIGINAL GAS PERRMIT IN THE APPLICATION
 FOLDER. GA
  