| Plan Review Notes For Permit 18050711 |
| Permit Number |
18050711 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-19 07:57:32 | | | | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF | | | THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING | | | THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) THE BTU LOAD OF THE RANGE DOES NOT CORRELATE WITH | | | THE BTU LOAD SHOWN UNDER PERMIT # 17111114. I HAVE | | | INCLUDED A COPY IN YOUR APPLICATION FILE TO BE USED AS | | | REFERENCE. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR. 2017 FBCR SEC. G2422.1 (8). | | | 5) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 | | | FBCR SEC.G2419.4. | | | 6) THE LONGEST RUN THAT IS LISTED ON THE GAS DRAWING | | | DOES NOT CORRELATE WITH THE ORIGINAL GAS PERMIT.SEE THE | | | COPY OF THE ORIGINAL GAS PERRMIT IN THE APPLICATION | | | FOLDER. GA | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|