| 2018-05-22 08:56:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEM NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED GENERATOR PAD ENGINEERING | | | REQUIRES THE GENERATOR TO HAVE A MINIMUM WEIGHT OF 526 | | | POUNDS. THE PROPOSED 22KW GENERAC GENERATOR WEIGHS 466 | | | POUNDS. |
|