| Plan Review Notes For Permit 18050682 |
| Permit Number |
18050682 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-18 09:11:17 | 1) SHOW THE CORRESPONDING EHD FOR EACH SECTION OF CSST | | | ON THE GAS DRAWING. | | | 2) THE SSIZE OF THE GALVANIZED LINE FROM THE GAS METER | | | IS UNDERSIZED TO THE IS UNDERSIZED PER TABLE 402.4 (2). | | | THE MAXIMUM BTU LOAD OF A 1 INCH GALVANIZED LINE AT 110 | | | FEET IS 173,000 BTU'S. THIS ONE INCH LINE MUST BE SIZED | | | FOR THE BTU LOAD OF THE TANKLESS WATER HEATER,THE | | | COOKTOP, THE GRILL AND THE DRYER.THIS LINE SHALL BE A | | | MINIMUM OF 1 1/4 INCHES. | | | 3) THE PLANS NOTE THE INTERIOR LOAD AS 317,000 BUT I | | | CALCULATE THE LOAD AS 68,000. THE EXTERIOR LOAD IS | | | LISTED AS 520,000 BUT I CALCULATE THE LOAD AS 649,000. | | | CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | | | | |
|