| 2018-05-29 10:41:37 | 1) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE PROPOSED | | | SHOWER. THE SHOWER SIZE AND DIMENSIONS SHALL COMPLY | | | WITH 2017 FBC-PLUMBING SEC.417.4. | | | 2) THIS BUILDING WAS CONSTRUCTED IN 2006 AND THEREFORE | | | WAS BUILT UNDER THE FAIR HOUSING ACT REQUIREMENTS. SHOW | | | THE REQUIRED CLEAR FLOOR SPACE ADJACENT TO THE SHOWER | | | AND PROVIDE THE LENGTH AND WIDTH DIMENSIONS AND THE | | | LOCATION OF THE CLEAR FLOOR SPACEE AS REQUIRED BY THE | | | FHA REQUIOREMENT #7. | | | 3) SHOW THE LOCATION OF THE SHOWER CONTROL VALVE FOR | | | THE PROPOSED SHOWER. | | | 4) PROVIDE DETAILS FOR THE REQUIRED REINFORCEMENT FOR | | | FUTURE GRAB BARS FOR THE PROPOSED SHOWER.SHOW THE TYPE | | | OF REINFORCEMENT MATERIAL, THE WIDTH OF THE | | | REINFORCEMENT AND THE MINIMUM AND MAXIMUM HEIGHT | | | DIMENSIONS OF THE REINFORCEMENT FROM THE FINISH FLOOR. | | | COMPLY WITH THE FAIR HOUSING ACT REQ. #6. | | | 5) SHT. 01 NOTES THE OCCUPANCY AS R-3. THIS IS | | | INCORRECT. REVISE THE OCCUPANCY TO READ R-2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|