| 2018-05-20 09:57:45 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN STATES THERE ARE NO CHANGES TO ELECRTICAL |
| | EXCEPT UPGRADING OF OUTLETS TO GFCI. HOWEVER, CONTRACT |
| | PROVIDED STATES THAT NEW LIGHTING IS BEING ADDED IN |
| | SEVERAL LOCATIONS. PROVIDE ELECTRICAL PLAN FOR REVIEW, |
| | SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR |
| | THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| | 471.025; WPB FBC 107.2.1, 107.3.5 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC |
| | 107.3.5 |
| | 3. SHOW ALL EXISTING RECEPTACLE OUTLETS IN KITCHEN AND |
| | BATHROOMS, PROVIDE AFCI AND GFCI PROTECTION WHERE |
| | APPLICABLE PER CODE. NEC 210.8, 210.12; FBC 107.2.1 |
| | 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |