| Plan Review Notes For Permit 18050621 |
| Permit Number |
18050621 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-27 12:48:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE ROOF PLAN IS ILLEGIBLE; PROVIDE A LEGIBLE PLAN | | | SHOWING LOCATION OF INSTALLATION. | | | | | | 2. TOO MANY DOCUMENTS WERE SUBMITTED. TWO DIFFERENT | | | PRODUCT APPROVALS WERE SUBMITTED WHICH APPEAR TO BE THE | | | SAME PRODUCT. | | | | | | SUBMIT ONE PRODUCT APPROVAL AND INDICATE WHICH ASSEMBLY | | | IS PROPOSED. | | | | | | 3. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | | RECORD PRIOR TO SUBMISSION, FBC 107. | | | | | | |
|