| 2018-10-04 11:32:37 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050617 |
| | 10/4/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REVISED SHEET P-1: ACCORDING TO THE MANUFACTURER'S |
| | SPECIFICATIONS THE AO. SMITH BT-80 GAS-FIRED WATER |
| | HEATER REQUIRES A NATURAL DRAFT CATEGORY I B-VENT NOT A |
| | CATAGORY III POSITIVE PRESSURE VENT AS THE DRAWING |
| | INDICATES. PLEASE CORRECT SND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE WATER HEATER AND VENT ASSEMBLY. |
| | |
| | 2) REVISED P-2: THE COMBUSTION AIR CALCULATIONS ARE |
| | INCORRECT- 24"X24"X7'-0" = 28 CUBIT FT. IF USING THE |
| | STANDARD METHOD UNDER SECTION 304.5.1 FBC FG THE |
| | REQUIRED VOLUME SHALL BE 50 CUBIT FT. PER 1,000 BTUH. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |