| 2018-10-11 09:01:24 | 3RD REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 3RD REQUEST PREVIOUS COMMENT NOT COMPLIED 2. TYPE OF |
| | GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC. 107.2.1. THE |
| | RESPONSE LETTER LIST THE TYPE OF GAS AS LP THE NOTE ON |
| | THE PLAN DOES NOT LIST A TYPE OF GAS IT DOES HAVE A |
| | SIZING TABLE FOR NATURAL GAS AND SHOWS A METER PLEASE |
| | PLACE NOTE ON THE GAS RISER TO CLARIFY. |
| | |
| | 2ND REQUEST NOT COMPLIED 3. PROVIDE ROOF PLAN SHOWING |
| | GAS PIPING . WPB AMEND. TO FBC SEC. 107.2.1 RESPONSE |
| | LETTER LIST A ROOF PLAN ON M-1 THERE IS NO ROOF PLAN |
| | SHOWN ON M-1 PROVIDE ROOF PLAN TO SHOW GAS PIPING, |
| | INLET OF COMBUSTION AIR DUCT AND EXHAUST PIPING AND |
| | MAKE UP AIR INTAKES WITH THE DIMENSIONS BETWEEN THEM. |
| | |
| | NEW COMMENTS: |
| | |
| | 1. PROVIDE DETAIL SHOWING DISTANCE BETWEEN INTAKE FOR |
| | COMBUSTION AIR DUCT EXHAUST VENT AND ANY OTHER INTAKES |
| | ON THE ROOF. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. THE SIZING TABLE IS FOR LESS THAN 2PSI BUT UNDER ONE |
| | OF THE NOTES FOR GAS IT LIST 2PSI PLEASE CLARIFY LIST |
| | PRESSURE ON RISER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |