| 2018-06-28 12:26:49 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. T-1 THE DESIGN CODES SHALLLL BE |
| | 2017 FLORIDA BUILDING CODE - BUILDING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE -PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - MECHANICAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | 2. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 3. SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS. THE SEAT |
| | HEIGHT OF A WATER CLOSET ABOVE THE FINISH FLOOR SHALL |
| | BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) |
| | MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS SHALL |
| | NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| | |
| | 4. SHT. P-2/ 018 DETAIL #2THE VENT SHALL RISE VERTICAL |
| | TO A POINT ABOVE FLOOD LEVEL RIM OF THE FLOOR DRAIN |
| | BEFORE IT CAN TURN AND RUN HORIZONTAL AND SHAL COMPLY |
| | WITH FBC PL 905.3, 905.4 |
| | |
| | 5. A BACKFLOW IS REQUIRED FOR THE ICE MACHINE, WATER |
| | FILTER, TEA BREWER AND CARBONATOR SHALL COMPLY WITH FBC |
| | PL 608.3, 608.16.10, 608.16.1 |
| | |
| | 6. SHT. P-3/019 THE VENT FOR THE FLOOR DRAIN AT THE |
| | DRINK MACHINE AND THE GREASE INTERCEPTOR SHALL RISE |
| | VERTICAL TO A POINT ABOVE FLOOD LEVEL RIM OF THE FLOOR |
| | DRAIN BEFORE IT CAN TURN AND RUN HORIZONTAL AND SHAL |
| | COMPLY WITH FBC PL 905.3, 905.4 |
| | |
| | 7. PROVIDE MANUFACTURE SPECIFICATION SHOWING A PIPING |
| | DETAIL OR A PIPING DETAIL ON THE PLAN FOR THE GREASE |
| | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHT. P-2 / 018 NOTE #2 THE MIXING VALVE SHALL |
| | CONFORM TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |