Plan Review Notes
Plan Review Notes For Permit 18050617
Permit Number 18050617
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-20 09:50:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050617
 6/20/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF THE RTU- SECTION 606.2.1 FBC M,
  
 2) M-1 & M-2: THE OUTSIDE AIR CALCULATIONS ARE
 INDICATING 0.7 CFMS OF O/A FOR THE KITCHEN, HOWEVER
 TABLE 403.3.1.1 REQUIRES AN EXHAUST SYSTEM FOR THE
 KITCHEN AT A RATE OF 0.70 CFMS PER SQ. FT. THERE IS NO
 EXHAUST SYSTEM SHOWN ON THE PLAN FOR THE KITCHEN.
  
 3) A-4, M-1, & M-2: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE OVEN/PROOFER AND REFER TO
 SECTION 507.3. A TYPE II HOOD IS REQUIRED FOR THE OVEN,
 OR IF A HOOD IS NOT REQUIRED PER THE MANUFACTURER, THEN
 AN EXHAUST SYSTEM SIZED AT 0.70 CFMS FOR 100 SQ. FT. OF
 THE OCCUPYING SPACE OF THE OVEN IS REQUIRED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  