| Date |
Text |
| 2018-06-28 14:34:39 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. THE GAS WATER HEATER SCHEDULE LIST THE WH AT |
| | 75,000BTU THE GAS RISER SHOWS IT AT 60,00BTU PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| | 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). |
| | |
| | 4. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | |
| | 5. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, |
| | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| | ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL |
| | GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 |
| | THROUGH G2439. |
| | |
| | 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 7. PROVIDE AN ENGINEERED DETAIL DRAWING FOR THE WATER |
| | HEATER STAND SHALL BE RATED TO A MIN OF 1000LB. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 8. USING THE SIZING TABLE LISTED ON THE PLAN 200 |
| | DEVELOPED LENGTH 132,00 BTU THE THE SYSTEM IS |
| | UNDERSIZED IT SHALL BE 11/4" UP TO THE FIRST TEE FOR |
| | THE RTU THEN 1" TO THE WATER HEATER. PER FBC FG TABLE |
| | 402.4(1) |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |