| Plan Review Notes For Permit 18050599 |
| Permit Number |
18050599 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-07 19:40:02 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PROVIDE INFORMATION REGARDING THE ELEVATOR LOBBY. IS | | | THIS REQUIRED TO BE AN ENCLOSED ELEVATOR LOBBY WITH | | | RATED WALLS, RATED DOORS? ARE THE ELEVATORS PRESSURIZED | | | SO THIS IS NOT REQUIRED? EITHER REVISE PLAN TO SHOW THE | | | 1 HOUR ELEVATOR LOBBY AND RATED DOORS, OR REVISE PLAN | | | TO NOTE APPLICABLE EXCEPTION, FBC 107. | | | | | | |
|